4.0 FLEXIBLE CONTROL STRATEGY
4.1 CS 1 SINGLE LOOP STANDARD PID
If Model Number 53MC51X1 has been purchased, the controller is shipped from the factory loaded
with the FCS CS 1 for Single Loop Standard PID. Other strategies are described in Section 4.3 of
Instruction Bulletin 53MC5000 . Figure 4-1 is a block diagram of this control strategy.
The default CS 1 set-up is as follows:
1. Flexible Control Strategy CS1 en-
abled.
(B00 = 1)
2. Proportional Band = 100%
(C106 = 100)
3. No Reset
(C107 = 0)
4. No Derivative
(C108 = 0)
5. No Alarms
(B335 = 1)
6. PV input, 1-5 V is 0 - 100%
(C256 = 100)
7. Reverse mode. That is, it expects
a control element such that increas-
ing the control output increases the
PV.
(L106 = 1)
8. Remote Set Point disabled
(L115 = 0)
9. Five displays:
POINT display of CON0
POINT with PV TREND of CON0
Tuning Parameters (PAR0)
Alarm Limits (PAR1)
System Status
To start up the controller in this mode:
1. Install the controller as described in Section 2; as a minimum the AI0 (PV) input and the AO0
(OUT) output must be connected.
2. Apply power to the controller
The controller should now be operating. A full description of the set-up is discussed in Section
4.1.2.
MODULAR CONTROLLER QUICK START