4.0 FLEXIBLE CONTROL STRATEGY

4.1 CS 1 SINGLE LOOP STANDARD PID

If Model Number 53MC51X1 has been purchased, the controller is shipped from the factory loaded
with the FCS CS 1 for Single Loop Standard PID. Other strategies are described in Section 4.3 of
Instruction Bulletin 53MC5000 . Figure 4-1 is a block diagram of this control strategy.
The default CS 1 set-up is as follows:

1. Flexible Control Strategy CS1 en-
abled.

(B00 = 1)

2. Proportional Band = 100%

(C106 = 100)

3. No Reset

(C107 = 0)

4. No Derivative

(C108 = 0)

5. No Alarms

(B335 = 1)

6. PV input, 1-5 V is 0 - 100%

(C256 = 100)

7. Reverse mode. That is, it expects
a control element such that increas-
ing the control output increases the
PV.

(L106 = 1)

8. Remote Set Point disabled

(L115 = 0)

9. Five displays:

POINT display of CON0
POINT with PV TREND of CON0
Tuning Parameters (PAR0)
Alarm Limits (PAR1)
System Status

To start up the controller in this mode:

1. Install the controller as described in Section 2; as a minimum the AI0 (PV) input and the AO0
(OUT) output must be connected.

2. Apply power to the controller

The controller should now be operating. A full description of the set-up is discussed in Section
4.1.2.

MODULAR CONTROLLER QUICK START

4-1