3.3.1.2 DISPLAYING A DATA BASE PARAMETER

To display a data base parameter press "D" and the parameter ID followed by . The current
value of the parameter will be displayed. The parameter ID is the data type specifier (B, L, C, H, F,
and A) and number of the point as shown in Section 7 of Instruction Bulletin 53MC5000.
For example, to see the value of B12, press:

D B12 .

The value presently assigned to B12 will be displayed.

Values displayed with the "D" command are formatted as follows:

B - three digit characters 000-255
L - one digit character 0 or 1
C & H - ten characters including digits, decimal point and sign (when negative). An excep-
tion is for the value of true zero, where the display consists of the three characters 0.0
F - five characters or less
A & Q - ten characters or less

Pressing after pressing "D" will automatically recall the last data base parameter ID used.

Pressing "N" after pressing "D" causes the next parameter of the same data type to be displayed.
(The NEXT command "N" only works with index numbers below 256.)

3.3.1.3 CHANGING A DATA BASE PARAMETER

To modify a value or enter a new value press "P" and the parameter ID followed by . Then
press the keys corresponding to the value to be assigned followed by .
For example, to set B0 to FIX 99 press:

P B0 099

Values entered with the PUT command "P" must be formatted as follows:

In general, all modification inputs are limited to the first ten characters of the field.
For B data type the value entered must be between 0 and 255.
For L data type the value must be 1 or 0.

All responses are completed by pressing .
Pressing after pressing "P" will automatically recall the last database parameter.
Pressing "N" after pressing "P" causes the next parameter of the same data type to be displayed.
(The NEXT command "N" only works with index numbers below 256.)

3.3.1.4 SETTING OR CHANGING A PASSWORD ("KEY")

As a security feature,the Modular Controller can be configured so that a password or "key" is
needed to change the controller’s configuration or F-CIM program in Engineering Mode using the
buttons on the front panel of the controller. These passwords or "keys" can only be accessed by
the Hand Held Configurer or the 53HC3300C software package.

MODULAR CONTROLLER QUICK START