4.1.4 CONTROL OPTIONS

4.1.4.1 REMOTE SETPOINT

1. Configure the RSP input signal parameters:

Set C257 to the span (in Engineering Units) of the RSP range.

Set C277 to the minimum (in Engineering Units) of the RSP range.

The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set L417=1.

The 53MC5000 is set to accept a linear PV signal. If square root extraction is
required, set L441=1.

2. Enable the Remote Setpoint capability by setting L115=1.

3. The 53MC5000 will permit remote setpoint operation if DI1 is closed.

4.1.4.2 FEEDFORWARD INPUT

Additive feedforward provides the ability to add a remotely generated analog value to the control
output of the PID controller:

1. Configure the FF input signal parameters:

Set C258 to the span (in Engineering Units) of the FF range.

Set C278 to the minimum (in Engineering Units) of the FF range.

The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L418=1.

The 53MC5000 is set to accept a linear PV signal. If square root extraction is
required, set L442=1.

4.1.4.3 OUTPUT TRACKING

The 53MC5000 is capable of forcing the control output to track an analog value based on the
status of a discrete input. This value can come from two sources; either an internal database loca-
tion or a remotely generated analog signal:

To track an internal database location:

1. Softwire the FCS Auto/Manual module to the internal value to be tracked by setting B160=129.

2. Set C129 to the desired value.

3. Enable Output Tracking by setting L119=1.

4. The 53MC5000 will track C129 only if DI0 is open (0 state).

To track a remotely generated analog signal (AI3):

1. Configure the RSP input signal parameters:

Set C259 to the span (in Engineering Units) of the OTV range.

Set C279 to the minimum (in Engineering Units) of the OTV range.