3.3.1.1 SETUP OF THE HAND HELD CONFIGURER

The Hand Held Configurer is shipped pre-configured to operate with the Controller. If the Config-
urer does not operate correctly, check the configuration by entering the Configurer’s set-up mode.
To enter set-up mode press and simultaneously. The correct configuration
is shown below.

BAUD = 9600
DATA BITS = 7

(not aplicable for U02 version)

PARITY = SPACE

(PARITY = NONE for U02 version)

DISPLAY PE ENABLED
REPEAT = FAST
ECHO DISABLED
HANDSHAKE DISABLED
SELF TEST DISABLED

If the configuration is not correct, it can be altered while in the Configurer’s set-up mode.

When set-up mode is entered the current baud rate setting is displayed on the top line; the follow-
ing choices are also displayed:

F1 Change Parameter
F2 Next
F3 Previous
F4 Quit
F5 Save

If the baud rate setting is incorrect, the setting can be changed by pressing F1. Each time the F1
key is pressed, an optional setting for the parameter on the top line of the display will be shown.
When the desired setting appears, press F2 to see the current setting for the next parameter (or F3
to see the setting for the previous one). If the setting is not correct, use F1 to cycle through avail-
able settings. All parameters can be checked and changed, if desired, in this way.

Pressing F4 (Quit) will exit set-up mode and any changes made will stay in effect until the Config-
urer is disconnected.

Use F5 to save changes to the controller’s memory; the Hand Held Configurer can then be discon-
nected and the changes will remain in effect.

MODULAR CONTROLLER QUICK START

3-19