STATE:
This is the current condition of the individual points (0 or 1).

NAME:
This is treated as a 10 character name of the point or two 5 character words. Each point of an SDM
has an associated name.

MODE:
This indicates how NAME is interpreted and displayed based on the points state. If a "0" name is
treated as a 10 character entry, when state is "1" the name is in reverse video, when state is "0"
the name appears normal. If a "1" name is divided into two 5 character words, the first 5 display
when state is "0", the second 5 when state is "1".

ALARM ENABLE:
When this value is "1" the HORN (L65) bit is set when the corresponding state goes from "0" to"1"
and the displayed name flashes as long as STATE = "1" and ALARM ACKNOWLEDGE = "0".

ALARM ACKNOWLEDGE:
This data is always forced to "0" when STATE is "0". When STATE is "1" and ALARM ENABLE is
"1" this point should be set to "1" to stop the flashing of the displayed name and to indicate that the
alarm condition has been recognized.

MODIFY DISABLE:
This will inhibit the operator from modifying the STATE of individual points through pushbutton ac-
tivity when set to "1". When set to "0" the operator can toggle the state of a point with the
pushbuttons.

DISPLAY:
This is the index number for the display that provides access through the status module.

MODULAR CONTROLLER QUICK START

3-39