The 53MC5000 is set to accept a 1-5 V RSP signal. If 0-5 V is required, set
L419=1.

The 53MC5000 is set to accept a linear PV signal. If square root extraction is
required, set L443=1.

2. Enable Output Tracking by setting L119=1.

3. The 53MC5000 will track AI3 only if DI0 is open (0 state).

MODULAR CONTROLLER QUICK START

4-6