DIGITAL FILTER INDEX :
In addition to the input filtering provided in hardware each input may have a first order digital filter
applied to its signal. The following table indicates the time constant for each index value.

0 No Smoothing

8 12.7s

1 0.05s

9 25.5s

2 0.1s

10 51.1s

3 0.3s

11 102s

4 0.7s

12 205s

5 1.5s

13 410s

6 3.1s

14 819s

7 6.3s

15 1638s

FREQUENCY INPUT:
This parameter (available only for AI4-7) specifies that the input signal is a pulse train whose
frequency is to be measured. The value of the input becomes (SPAN x FREQUENCY) + ZERO.

PULSE COUNT:
When the input is configured for a frequency input this value represents the total number of pulses
applied to the analog input terminals. The count value automatically resets to 0.0 when it reaches
10,000,000.

TAG NAME:
A user assigned name for the AI can be loaded into this parameter.

ENGINEERING UNITS:
The units of measure the AI represents can be loaded into this parameter.