2551 Magmeter

The values shown for each menu item represent the factory standard
setting. All 2551 magmeters are packaged with these settings.

The menu repeats for Relay 2 and Relay 3.

Hysteresis

Time

Low Setpoint

Process

Relay activated

Relay deactivated

Hysteresis

Time

High Setpoint

Process

High Limit

Hysteresis

Hysteresis

Window

Time

Low Limit

Process

9.3 High, Low, or Window Relay modes
Program the relay to activate when the À ow rate reaches a setpoint (High or Low) or when the À ow
rate moves outside of a prescribed range (Window).

Reverse Flow
The setpoint values for HIGH, LOW and WINDOW modes can be set to negative values if required.
For example, a LOW alarm might be set to activate if the À ow rate falls to -10 GPM.

Set High: Set the À ow rate where a High relay will be activated.

Set Low: Set the À ow rate where a Low relay will be activated.

Hysteresis: Set a À ow rate increment where the relay will be
deactivated. The hysteresis setting serves to prevent relay
"chatter" when the À ow rate recovers from an alarm condition by
requiring the low rate to move substantially within the setpoint.

Delay: Set a time period for the relay to wait after reaching the
setpoint. This delay serves to prevent the relay "chatter" by
allowing the À ow rate time to move back within the setpoint.

Relay 1 Mode

Low >

Relay 1 Mode

High >

Relay 1 Mode

Window >

Relay 1 Set Low

00.000 GPM >

Relay 1 Set High

00.000 GPM >

Relay 1 Set Low

00.000 GPM >

Relay 1 Hys

00.000 GPM >

Relay 1 Delay

0.1 secs >

Relay 1 Set High

00.000 GPM >

Relay 1 Hys

00.000 GPM >

Relay 1 Delay

0.1 secs >

Relay 1 Hys

00.000 GPM >

Relay 1 Delay

0.1 secs >

3s

ENTER

Or

Signet Magmeter

RELAY 1

RELAY 2

ENTER

1234.56 GPM

876543.21 >

Enter Menu

>

Enter Menu

Setup

>

Enter Menu

Calibration

>

Enter Menu

Relay 1

>

NOTE: The Security Code
must be entered before
modifying the relay menu.

Enter Code

0000

Relay behavior with LOW Setpoint

Relay behavior with HIGH Setpoint

Relay behavior with WINDOW Setpoints