beautypg.com

Burkert Type 8056 User Manual

Page 77

background image

- 77 -

RS232_485_ETP_MODBUS_BU_REV02.doc

don’t have practical effect. To every address a various function corresponds. The code number for

“on” is FF00 (hex), for “off” is 0000. Others values product the exception n.3.


Addresses(Hex format)

Function Description

0000

start / stop batch

0001 reset

batch

0002 reset

totalizers

0003

reset data logger

0004

reset events logger


NOTE: for reading the index value of the batch memory is necessary to activate the

batch function.
If the batch function is disabled the system return the exception code n. 4.

FUNCTION 08, standard diagnose function of the MODBUS protocol. The following table lists the

sub-commands:

Addresses (Hex format)

Function Description

0000

return query data

0001 restart

communications

0004

listen mode only

000A clear

counters

000B-0012 return

counters

value



FUNCTION 16, function for to set parameters in the converter. As the same way as the reading

function, it is possible to write value in the memory of the meter in the format of 16 bit variables
that can be append together to form floating point variables (float) or long-integer (long) with 32

bit. The high side (MSW) start at even address, the low side (LSW) start immediately the following.
The addresses are expressed in hex format.

Addresses (Hex format)

Function Description

07D0-084F

Values batch memory, grouped in 64 contiguous blocks

of 8 register of memory at 16 bit for every block.

0BB8

Batch Memory index current in use

For the meaning of the memory location and their address go to the relative reading section.

5.8.

CUSTOM FUNCTION

FUNCTION 110, execution of the ETP command. With this function it is possible to send a text

string to the meter in the ETP protocol format (see the relative section), the ETP command is
embedded in the MODBUS standard protcol format.
The max length of the string to send is 251 characters. The returned string form the meter is

embedded with the same structure. Also in this case the max length of the returned string is 251
characters.

With the ETP command is possible to set and to return the value of every parameter of the
converter.
For the complete list of the ETP commands see the relative section.

This manual is related to the following products: