Burkert Type 8056 User Manual
Page 37

- 37 -
RS232_485_ETP_MODBUS_BU_REV02.doc
Help command: MFMXT=?
min <> max (units)
if accepted
5:ACCESS ERR if insufficient access
level
Read command: MFCUT?
Value of measure cut-off thr. if
accepted
5:ACCESS ERR if insufficient access
level
Set command: MFCUT=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
MFCUT (Measure Filter Cut-off
Threshold) Reads or sets the value
of the measure filter cut-off
threshold.
Help command: MFCUT=?
min <> max (units)
if accepted
5:ACCESS ERR if insufficient access
level
Read command: ACALE?
Enable/disable status if accepted
5:ACCESS ERR if insufficient access
level
Set command: ACALE=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
ACALE (Auto-CALibration Enable)
Enables or disables the auto-
calibration feature of the
instrument.
Help command: ACALE=?
List of
num:description
if accepted
5:ACCESS ERR if insufficient access
level
Read command: ARNGE?
Enable/disable status if accepted
5:ACCESS ERR if insufficient access
level
Set command: ARNGE=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
ARNGE (Auto-RaNGe Enable)
Enables or disables the auto-range
feature of the instrument.
Help command: ARNGE=?
List of
num:description
if accepted
5:ACCESS ERR if insufficient access
level
Read command: ENSVE?
Enable/disable status if accepted
5:ACCESS ERR if insufficient access
level
Set command: ENSVE=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
ENSVE (ENergy-SaVing Enable)
Enables or disables the energy-
saving feature of the instrument.
Help command: ENSVE=?
List of
num:description
if accepted
5:ACCESS ERR if insufficient access
level
Read command: ENSST?
Value of measure sampling time if
accepted
5:ACCESS ERR if insufficient access
level
Set command: ENSST=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
ENSST (ENergy-Saving Sample
Time) Reads or sets the value of
the measure sampling time when
the energy-saving feature is active.
Help command: ENSST=?
min <> max (units)
if accepted
5:ACCESS ERR if insufficient access
level