Burkert Type 8056 User Manual
Page 31

- 31 -
RS232_485_ETP_MODBUS_BU_REV02.doc
Set command: CKLP0=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
or sets the value for the six
coefficients for the linearization of
the positive flow rate range.
NOTE: the examples refer to the
command CKLP0, but the others
are the same
Help command: CKLP0=?
min <> max
if accepted
5:ACCESS ERR if insufficient access
level
Read command: CKLN0?
Value of the coefficient if accepted
5:ACCESS ERR if insufficient access
level
Set command: CKLN0=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
CKLN0, CKLN1, CKLN2, CKLN3,
CKLN4, CKLN5 (Coefficient KL
Negative 0, 1, 2, 3, 4 an 5) Reads
or sets the value for the six
coefficients for the linearization of
the negative flow rate range.
NOTE: the examples refer to the
command CKLN0, but the others
are the same
Help command: CKLN0=?
min <> max
if accepted
5:ACCESS ERR if insufficient access
level
SFREQ (Sampling FREQuency)
Reads or sets the measure sampling
frequency of the instrument.
Read command: SFREQ?
Value of the measure sampling
frequency
5:ACCESS ERR if insufficient access
level
Read command: CRVRF?
Value of the coil regulator voltage
reference
5:ACCESS ERR if insufficient access
level
CRVRF (Coil Regulator Voltage
ReFerence) Reads or sets the value
of the reference for the coil current
regulator.
Help command: CRVRF=?
min <> max
if accepted
5:ACCESS ERR if insufficient access
level
Read command: CRRMA?
Value of the coil regulator margin
5:ACCESS ERR if insufficient access
level
CRRMA (Coil Regulator Regulation
MArgin) Reads or sets the value of
the regulation margin for the coil
current regulator.
Help command: CRRMA=?
min <> max
if accepted
5:ACCESS ERR if insufficient access
level
Read command: EPDEN?
State of the pipe detection circuit
5:ACCESS ERR if insufficient access
level
Set command: EPDEN=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
EPDEN (Empty Pipe Detection
ENable) Enables or disables the
empty pipe detection circuit.
Help command: EPDEN=?
0:OFF,1:ON if accepted
5:ACCESS ERR if insufficient access
level
Read command: EPDGV?
Value of the empty pipe detection gain
5:ACCESS ERR if insufficient access
level
EPDGV (Empty Pipe Detection
Gain Value) Reads or sets the value
of the gain for the empty pipe
detection circuit.
Help command: EPDGV=?
min <> max
if accepted
5:ACCESS ERR if insufficient access
level