Name and description

Modes

Returned values or codes

Read command: OUT1F?

Type of function if accepted

1:CMD ERR if digital outputs not
enabled

5:ACCESS ERR if insufficient access
level

Set command: OUT1F=

n

0:OK if parameters accepted

1:CMD ERR if digital outputs not
enabled

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access
level

OUT1F (OUTput 1 Function) Sets

the function type related to the
digital output 1. Valid only if the

digital outputs are installed and
enabled.

Help command: OUT1F=?

List of

num:description

if accepted

1:CMD ERR if digital outputs not

enabled
5:ACCESS ERR if insufficient access
level

Read command: OUT2F?

Type of function if accepted
1:CMD ERR if digital outputs not
enabled

5:ACCESS ERR if insufficient access
level

Set command: OUT2F=

n

0:OK if parameters accepted
1:CMD ERR if digital outputs not
enabled

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access

level

OUT2F (OUTput 2 Function) Sets
the function type related to the
digital output 2. Valid only if the

digital outputs are installed and
enabled.

Help command: OUT2F=?

List of

num:description

if accepted

1:CMD ERR if digital outputs not

enabled
5:ACCESS ERR if insufficient access
level

Read command: OUTIS?

Type of function if accepted
1:CMD ERR if digital outputs not

enabled
5:ACCESS ERR if insufficient access
level

Set command: OUTIS=

n

0:OK if parameters accepted
1:CMD ERR if digital outputs not
enabled

2:PARAM ERR if

n

out of range

5:ACCESS ERR if insufficient access

level

OUTIS (OUT Immediate State)
function for set in direct way the

value of the digital outputs

Help command: OUTIS=?

List of

num:description

if accepted

1:CMD ERR if digital outputs not

enabled
5:ACCESS ERR if insufficient access

level

CO1FS (Current Output 1 Full
Scale) Sets the full scale value for

the current output 1: it can be 20
or 22 mA. Valid only if the current

output1 is installed and enabled.

Read command: CO1FS?

Full scale value if accepted
1:CMD ERR if current output not

enabled
5:ACCESS ERR if insufficient access

level

This manual is related to the following products: