- 55 -
RS232_485_ETP_MODBUS_BU_REV02.doc
Set command: MSIEN=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
Help command: MSIEN=?
List of
num:description
if accepted
5:ACCESS ERR if insufficient access
level
Read command: STBYC =?
List of
num:description
if accepted
5:ACCESS ERR if insufficient access
level
STBYC (STandBY Command) set
converter in stand-by mode
Once this command is issued ,
the only way to wakeup the
converter is by the keyboard
Set command: STBYC =
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
COMMANDS AND FUNCTIONS EQUIVALENT TO THE “11-INTERNAL DATA” MENU
Name and description
Modes
Returned values or codes
Read command: L2ACD?
Programmed code if accepted
5:ACCESS ERR if insufficient access
level
Set command: L2ACD=
n
0:OK if parameters accepted
2:PARAM ERR if
n
out of range
5:ACCESS ERR if insufficient access
level
L2ACD (Level 2 Access CoDe)
Reads or sets the level 2
programmable access code. It can
be set to zero to disable all L2
access requests. WARNING: do
not forget the code entered!
Help command: L2ACD=?
min <> max
if accepted
5:ACCESS ERR if insufficient access
level
Read command: NOT
SUPPORTED
1:CMD ERR if command is issued
Set command: LFDIC=1
0:OK if parameters accepted
2:PARAM ERR if
n
not equal to 1
3:EXEC ERR if default data corrupted
5:ACCESS ERR if insufficient access
level
LFDIC (Load Factory Defaults
Immediate Command) Loads the
factory default parameters.
WARNING: all the current
working parameters eventually
modified by the user will be
lost!
Help command: LFDIC=?
1:EXECUTE
if accepted
5:ACCESS ERR if insufficient access
level
Read command: NOT
SUPPORTED
1:CMD ERR if command is issued
Set command: LUDIC=1
0:OK if parameters accepted
2:PARAM ERR if
n
not equal to 1
3:EXEC ERR if user data corrupted
5:ACCESS ERR if insufficient access
level
LUDIC
(Load
User
Data
Immediate Command) Loads the
user preset parameters.
WARNING: all the current
working parameters eventually
modified by the user will be
lost!
Help command: LUDIC=?
1:EXECUTE
if accepted
5:ACCESS ERR if insufficient access
level
Read command: NOT
SUPPORTED
1:CMD ERR if command is issued
SUDIC
(Save
User
Data
Immediate Command) Saves the
current working parameters as user
preset data.
Set command: SUDIC=1
0:OK if parameters accepted
2:PARAM ERR if
n
not equal to 1
3:EXEC ERR if memory failure
5:ACCESS ERR if insufficient access
level