Burkert Type 8056 User Manual
Page 76
- 76 -
RS232_485_ETP_MODBUS_BU_REV02.doc
The returned values are at FFFFFFFF (hex) when the request data is not valid in the
data logger (data not still collected).
NOTA: when the value of the single long-integer variable, which contains the event
flags, is 000300FF (hex) the meaning is a ‘Restart of the converter’ and the single bit
has not significant.
Batch memory values
Addresses(Hex format)
Description
07D0-07D7
Data block memory batch n. 0
07D8-07DF
Data block memory batch n. 1
… …
… …
… …
0848-084F
Data block memory batch n. 15
In the following table there is the structure of the data refer to the first batch memory, the other
memories are the same but in different addresses.
Addresses(Hex format)
Description
07D0-07D3
Name of the product refer to the batch memory
(8 length string characters)
07D4
Counter of the number of batch with this
product
07D5
Safety timer value in tenths of second (10 =
1.0 seconds)
07D6-07D7
Batch value in technical (long)
NOTE: for reading the batch memories is necessary to set ON the Batch function, batch
function.
If the batch function is disabled the system return the exception code n. 4.
Index value of the batch memory current in use
Addresses(Hex format)
Description
0BB8
Index value of the batch memory current in use
NOTE: for reading the index value of the batch memory is necessary to activate the
batch function.
If the batch function is disabled the system return the exception code n. 4.
• FUNCTION 05, execution of command of type on/off. For the standard MODBUS, this function is
used only for set the state of variable type “coil” or bit, in this context the function of the variable
is for change the activation state of a specific function. The two 16 bit words that follow the
command are used for indicate the function type (address) and action (on or off). The “off” action