beautypg.com

Burkert Type 8056 User Manual

Page 76

background image

- 76 -

RS232_485_ETP_MODBUS_BU_REV02.doc

The returned values are at FFFFFFFF (hex) when the request data is not valid in the
data logger (data not still collected).

NOTA: when the value of the single long-integer variable, which contains the event
flags, is 000300FF (hex) the meaning is a ‘Restart of the converter’ and the single bit

has not significant.



Batch memory values

Addresses(Hex format)

Description

07D0-07D7

Data block memory batch n. 0

07D8-07DF

Data block memory batch n. 1

… …
… …
… …
0848-084F

Data block memory batch n. 15



In the following table there is the structure of the data refer to the first batch memory, the other

memories are the same but in different addresses.


Addresses(Hex format)

Description

07D0-07D3

Name of the product refer to the batch memory

(8 length string characters)

07D4

Counter of the number of batch with this
product

07D5

Safety timer value in tenths of second (10 =
1.0 seconds)

07D6-07D7

Batch value in technical (long)

NOTE: for reading the batch memories is necessary to set ON the Batch function, batch
function.

If the batch function is disabled the system return the exception code n. 4.

Index value of the batch memory current in use

Addresses(Hex format)

Description

0BB8

Index value of the batch memory current in use

NOTE: for reading the index value of the batch memory is necessary to activate the

batch function.
If the batch function is disabled the system return the exception code n. 4.

FUNCTION 05, execution of command of type on/off. For the standard MODBUS, this function is

used only for set the state of variable type “coil” or bit, in this context the function of the variable
is for change the activation state of a specific function. The two 16 bit words that follow the
command are used for indicate the function type (address) and action (on or off). The “off” action

This manual is related to the following products: