Burkert Type 8056 User Manual
Page 59

- 59 -
RS232_485_ETP_MODBUS_BU_REV02.doc
its technical measure unit. Returns
two comma-separated fields, the
technical unit symbol and the
numeric value.
Help command: NOT
SUPPORTED
1:CMD ERR if command is issued
Read command: CUTPV? Returns
currency-symbol,value
string
1:CMD ERR if currency mode not
enabled
Set command: NOT
SUPPORTED
1:CMD ERR if command is issued
CUTPV
(CUrrency
Totalizer
Positive
Value) Reads the
converted currency value relative
to the partial positive totalizer and
its currency unit. Returns two
comma-separated fields, the unit
symbol and the numeric value.
Help command: NOT
SUPPORTED
1:CMD ERR if command is issued
Read command: CUTNV? Returns
currency-symbol,value
string
1:CMD ERR if currency mode not
enabled
Set command: NOT
SUPPORTED
1:CMD ERR if command is issued
CUTNV
(CUrrency
Totalizer
Negative
Value) Reads the
converted currency value relative
to the partial negative totalizer and
its currency unit. Returns two
comma-separated fields, the unit
symbol and the numeric value.
Help command: NOT
SUPPORTED
1:CMD ERR if command is issued
Read command: AIN1V? Returns
measure-unit,value
string
1:CMD ERR if analog input 1 not
enabled
Set command: NOT
SUPPORTED
1:CMD ERR if command is issued
AIN1V (Analog INput 1 Value)
Reads the value of the analog
input 1 and its associated technical
unit. Returns two comma-
separated fields, the unit symbol
and the numeric value.
Help command: NOT
SUPPORTED
1:CMD ERR if command is issued
Read command: BATTS? Returns
%,value
string
Set command: NOT
SUPPORTED
1:CMD ERR if command is issued
BATTS (BATTery Status) Reads
the estimated residual capacity of
the battery. Returns the percent
symbol and value separated by the
comma.
Help command: NOT
SUPPORTED
1:CMD ERR if command is issued
Read command: ALARM? Returns all active alarms in CSV format
Set command: NOT
SUPPORTED
1:CMD ERR if command is issued
ALARM (ALARM status) Reads
the alarm status of the instrument.
Returns a CSV list of all active
alarm.
Help command: NOT
SUPPORTED
1:CMD ERR if command is issued
AUXILIARY SET COMMAND
Name and description
Modes
Returned values or codes
Read command: ACODE?
Required access level: 2
String value if command accepted
1:CMD ERR if GPRS not enabled
5:ACCESS ERR if insufficient access level
Set command: ACODE
=
string
0:OK if parameters accepted
1:CMD ERR if GPRS not enabled
2:PARAM ERR if
string
out of range
5:ACCESS ERR if insufficient access level
ACODE (Access CODE)
Help command: ACODE
=?
NUMERIC RANGE if accepted
1:CMD ERR if GPRS not enabled
5:ACCESS ERR if insufficient access level
MODSV (MODel and Software
Version)
Read command: MODSV?
String value if command accepted
1:CMD ERR if GPRS not enabled
5:ACCESS ERR if insufficient access level
CLIST(Command LIST)
Read command: CLIST?
String value if command accepted
1:CMD ERR if GPRS not enabled
5:ACCESS ERR if insufficient access level