Wiring the TS-DIM to a T5 Series Console

Turn off the main power source/all power sources that terminate in the console before working on or servicing this 

equipment. Failure to do so will create a lethal electrical shock hazard.

1. Make sure all power to the T5 Series console is turned off at the power source.
2. Locate the Communication Ports on the T5 series console.
3. Terminate the wires as follows:

a. Wire 485A to Terminal 485A Blue

b. Wire 485B to Terminal 485B Black

c. Wire S.RTN to Terminal GND Orange

Note: There may be RS-485 interface wires already connected to the terminals. In this case, remove the wire(s) and twist 

them together with the appropriate TS-DIM wire. Reinsert these into the correct terminal and tighten the screw.

Figure 21: TS-DIM Wiring Connection

In the T5 series programming, Modules Expected must be set to DIM 2.

Figure 22: Set Modules Expected

RS-485 must be enabled

Figure 23: Enable RS-485