beautypg.com

Programming the tank gauge – Franklin Fueling Systems TS-DIM User Manual

Page 24

background image

24

Programming the Tank Gauge

NO. METERS:  The total number of all Fueling Point Meters at the site. This is located under the SYSTEM menu. A value 

above 0 will show the following menus:
RECONCILE: Enables reconciliation by programming schedule and time for gathering data. Located under the SETUP menu.
DIM Dispenser Interface: Program Meters, Fuel Points, and DIM address. This is located under the SETUP menu
REPORTS...RECONCILE: Program a schedule on a Shift basis, Daily schedule, Monthly basis, Shift History, or Daily 

History — the RECONCILE menu is DIM-related and replaces the earlier Non-DIM Inventory Reconciliation menu 

(reconcile is the last of the report choices)

TS-DIM Related Features
Sales and Delivery adjustment (in volume units) are available on a per-tank basis. These offsets allow adjustment to a 

known discrepancy in reconciliation (e.g. when calibrating a meter, or when a product delivery doesn’t match the reported 

delivery at the tank gauge).
Press MENU – DOWN – and M1 for SALES ADJ or M2 for DELIV ADJ.

SETUP

SYSTEM

Setup Menu

NO. METERS = 0

DIMM

METERS (100 meters supported)

METER N (shown typical)

DISPENSER INTERFACE

RECONCILE

SCHEDULE

TIME = 23:00:00

NONE
DAILY
SHIFT

Shift 1 = 7:00:00

HH:MM:SS 24 Hour Format Input time

Shift 2 = 15:00:00

HH:MM:SS 24 Hour Format Input time

HH:MM:SS 24 Hour Format

Input time (N/A for Shift)

Shift 3 = 23:00:00

HH:MM:SS 24 Hour Format Input time

(For 2 shifts, use same time for shift 2 & 3)

Input the total number of meters

at the site. (TS-DIM(s) sites)

Some prior-input values will be

present...correct as needed

FUEL PTS Fueling Points

FUEL PT = N

Fuel Point # from WinTester data

GRADE NO. = N

TANK A = N

Grade from WinTester data

FUEL PTS N Fueling Point N (shown typical)

DIM UNIT DIM Unit Number

Correct TS-DIM number

- FUEL PT = 1

DIM FL PT DIM Fueling Point

Correct Fuel Point # as req’d

- FUEL PT = N

Tank No. (Largest % of a blend)

TANK B = 0

Tank No. (Smallest % of a blend)

BLEND = 100

Blending Ratio % from Tank A

Input the correct Tank Number for Tank A & Tank B

Figure 19: Tank Gauge DIM Menu