beautypg.com

Franklin Fueling Systems TS-DIM User Manual

Page 11

background image

11

TS-DIM/G Adapter Cable

(P/N 600-0201)

TS-DIM/G

TS-DIM/G Console

to Controller

Connector

(P/N 601-1004)

DB9 to RJ45

Adapters

Gilbarco

Dbox

PA03060020

Connector

(P/N 601-1003)

TS-DIM/G to Gilbarco DBox PA03060020

Figure 8

Pump-Specific Installation — TS-DIM / GS for Gilbarco MOC G-SITE Systems

If the Gilbarco system uses a MOC G-SITE point of sale system, special procedures must be followed to successfully 

install a TS-DIM. Both the type of controller (C2, 486, Pentium, etc.) the G-SITE is using and the revision number of the 

software running on the G-SITE are very important to know for installation and should be entered on a thorough site 

survey.
Confirm that the G-SITE will support the EMC tank monitoring option which is a component of the BIR (Business Inventory 

Reconciliation) interface. The software revision number, along with MOC type, indicate the ability of the G-SITE to support 

this function. If the G-SITE does not have the correct revision software loaded, a software update is required from an 

authorized Gilbarco distributor. If the G-SITE is EMC ready, proceed with TS-DIM installation. Otherwise, contact your 

dealer for further assistance.
Follow the instructions in the TS-DIM General Installation section and perform general installation procedures and 

preliminary tests using the internal DIM Diagnostics (page 19).
Proceed with installing the TS-DIM and refer to the TS-DIM Adapter Board Jumper Selections Diagram (Figure 2).

1.   Verify that the adapter board’s SW1 jumpers are set for Gilbarco G-SITE models.
2.   Set a jumper on position SW2 of the adapter board for RS232 full duplex. Plug the adapter harness onto 

position J3.

3.   Referencing the G-SITE installation manual, locate the G-SITE controller EMC tank monitor port. Connect the TS-

DIM to the G-SITE using the P / N 600-0205 cable and the RJ45 adapters P / N 601-1002).

Note:  If G-Site is using C2 Style controller contact Tech Support for the correct parts and instructions.

 Refer to Diagrams: TS-DIM to Gilbarco 486 G-SITE at the end of this section for more information.

Note: Some installations may require a longer cable than P / N 600-0205 or P / N 600-0207. If this is the case, FFS 

recommends that the technician use a standard CAT5 cable (of any length) to replace the cable going from the TS-

DIM to the G-Site.

4.   Return to the TS-DIM Installation Section for remaining system installation procedures.

The TS-DIM G-SITE reports all totals by meter number for each fueling position. Blender dispensers will report meter 1 to

hose 1 and meter 2 to hose 2 position on the TS-DIM. A blended product will report an increase for both meters.