beautypg.com

General technical information – Franklin Fueling Systems TS-DIM User Manual

Page 26

background image

26

Table 3 Gilbarco MOC G-SITE

Problem

Recommendation / Analysis

No data capture.

• Is the EMC port on G-SITE enabled?

• Is the correct software version being used on G-SITE?

• Is the adapter cable into the correct port on G-SITE?

• Is the correct type of adapter being used?

Refer to the TS-DIM Adapter Board Jumper Selections Diagram.

TS-DIM is not answering G-SITE.

• Are the settings correct on the adapter board? Refer to Figure 2 to check them.

All communications down on con-

sole / POS to pumps.

• Adapter cable not connected.

• Adapter cable connected incorrectly.

• Wrong type adapter communications input used - RS422 / current loop (refer to the  TS-DIM 

for Gilbarco Electronic Dispenser section of this manual).

• Defective cable.

Table 4 Tokheim

Problem

Recommendation / Analysis

Console to dispenser communi-

cation shuts down when adapter 

cable is connected.

• May have wrong version adapter board in TS-DIM / T (RS422 or standard)

LEDs are off and never flash.

• Test twist-lock connectors for tightness.

• Adapter cable is connected incorrectly.

• Wrong type of adapter communications input used — RS422 / current loop. For standard 

operation, connect adapter harness to J3 and place jumpers on JP1. For RS422 operation, 

connect adapter harness to J2 and place jumpers on JP2.

• Defective cable.

Only one LED is flashing (D2 or D3) • Check all cable connections.

Table 5 Wayne / Dresser

Problem

Recommendation / Analysis

Data is not captured correctly for 

one or more of the dispensers.

• Check both loops on the adapter cable at position J2 on the adapter board to see if they are 

wired correctly.

• Check normal / bypass switch, is it Normal?  See Figure 14.

Console to dispenser communica-

tion shuts down when the adapter 

cable is connected.

• Adapter cable (should be in position J2) may be connected incorrectly.

• Loop wires in the DBox may be wired incorrectly (see Figure 14).

LEDs are not flashing.

• Make sure that both loops on the J2 adapter cable are wired correctly.

• Adapter cable may be connected incorrectly.

• Wrong pump type may be selected.

• Check the normal / bypass switch, is it Normal?  See Figures 1 &14.

Note:

*

= With volt meter set on a 10 VDC scale, place test probes on MR line and common. With MR switch inactive 

(pump off), your meter should read approximately 8 VDC. With MR switch active (pump running), your meter 

should read approximately 0 VDC.

General Technical Information

This section contains miscellaneous information which may be useful in installing and troubleshooting the external TS-

DIM. Refer to the appropriate sections and diagrams in this manual for more specific information.

Table 8 TS-DIM General Specifications

Physical Size

 7.5" x 8.5" X 2"

Operating Temperature

 32 to 120 degrees F

Storage Temperature

 32 to 120 degrees F

Electrical Requirements  115 VAC, 20 W Maximum (dedicated circuit with earth bond)