Gilbarco

G-SITE

Controller

C2 Style

TS-DIM/GS

RJ45 to DB9 Adapter

(P/N 601-1002)

RJ45 to DB25 Adapter

(P/N 601-1001)

Note: If the 600-0205 cable is not long enough for your installation, a standard CAT5

cable may be substituted.

TS-DIM/GS to Gilbarco C2 G-SITE

Gilbarco

G-SITE

Controller

486 Style

or Passport

TS-DIM/GS

RJ45 to DB9 Adapter

(P/N 600-1005)

TS-DIM/GS G-SITE Adapter Cable

(P/N 600-0205)

Note: G-SITE systems must support EMC with BIR interface. Minimum software

levels must exist on the G-SITE for proper operation.

TS-DIM/GS to Gilbarco 486 G-SITE or Passport

TS-DIM/GS G-SITE Adapter Cable

(P/N 600-0205)

Note: G-SITE systems must support EMC with BIR interface. Minimum software

levels must exist on the G-SITE for proper operation.

Figure 9

Port 5

Dongle Cable

Gilbarco Part # M09747B010

PassPort 8.02

TS-DIM/GS

Dispenser Security Hub

Part # 600-0205

601-1002

601-1005

Gilbarco Passport

1.  Using TSP-GSDCBL connect the 600-1002 adaptor to the port on the TS-DIM/GS.
2.  Connect the 600-1005 to the end of the dongle cable Gilbarco Part # M09747B010
3.  Connect the dongle cable to Port on Dispenser Security Hub (port 5) if available
4.  Setup EMS DIM 1 to G site and RS232/Duplex
5.  Be sure Port on Security hub is set to EMC and Baud 1200, 7, E, 1
6.  Query Dispensers.