9 update firmware, 1 update firmware using telnet or serial line, Uploaded file found, checking md5 sum – GE Industrial Solutions ADVANCED SNMP WEB INTERFACE CARD User Manual
Page 29: Waiting for reset (watchdog or manual)

Modifications reserved
Page 29/33
OPM_CNT_ADV_SNM_CRD_XGB_V050.doc
Operating Manual ADVANCED SNMP / WEB INTERFACE CARD
9 UPDATE
FIRMWARE
The SNMP card gives the possibility to update the firmware via LAN using a FTP server.
9.1 UPDATE FIRMWARE USING TELNET OR SERIAL LINE
Here, the necessary steps to update the firmware using Telnet or serial line:
1. Check the version of the firmware at the top of the setup menu (vZ.ZZ = firmware version, bX.XX
backup version):
--<>----[MAC=00:50:c2:09:70:02]-----------
2. Enable the FTP server typing the key “L” in the setup menu
GE> L
FTP Server Ready. Ftp the image and press Enter.
3. FTP the new version of the firmare.
This step can be accomplished using a windows FTP program or using DOS commands as follows:
C:\>ftp XXX.XXX.XXX.XXX [Enter]
Connected to XXX.XXX.XXX.XXX
220 FTP Server (Version 1.0) ready.
User (XXX.XXX.XXX.XXX :(none): [Enter]
230 User logged in, proceed.
ftp> bin
200 Command okay.
ftp> put
200 Command okay.
150 File status okay; about to open data connection
226 Closing data connection. Requested file action successful.
XYXYXY nytes sent in ZZ,ZZ seconds (XYXY Kbyte/sec)
ftp> bye [Enter]
221 Service closing control connection. Logged out if appropriate.
C:\>
4. Press the key “Enter” in the setup menu.
Avoid after this step to reset or disconnect the card!
If the connection with the setup menu has been established using Telnet, after this step the
connection is lost, otherwise if the connection has been established using RS232, the following
screen appears in the setup menu:
Uploaded file found, checking md5 sum
MD5 sum ok. Flashing file: XXXXXXXXXX
Please wait. After flashing, the card will be restarted.
. Starting sector erase
. Waiting for completion
. Starting programming
. Waiting for completion
. Ok! Waiting for reset
----------
Waiting for reset (watchdog or manual).
5. Wait about 30 sec. to permit the card to update the software and then check if the version of the
firmware has changed.
--<>----[MAC=00:50:c2:09:70:02]-----------