GE Industrial Solutions ADVANCED SNMP WEB INTERFACE CARD User Manual
Page 16

Modifications reserved
Page 16/33
OPM_CNT_ADV_SNM_CRD_XGB_V050.doc
Operating Manual ADVANCED SNMP WEB INTERFACE CARD
R. Clear reset count
Syntax:
GE>R
Description:
Clear the reset counter, which holds the number of times the board has been resettled.
S. Ethernet
Syntax:
GE> S
Ethernet mode (0=Auto, 1=10/100TP, 2=10TP/BNC, 3=BNC, 4=100TP, 5=10TP) [0]:
X
[Enter]
Default:
0 = Auto
Description:
Defines how the board should detect the correct Ethernet interface.
-
Setting this parameters to zero (0), forces a full auto detection
-
Setting this parameters to one (1), restricts the detection to the RJ45 connector (10 BASE-T or 100 BASE-TX)
-
Setting this parameters to two (2), restricts the detection to 10 Mbits (10 BASE-T or BNC)
-
Setting these parameters to 3, 4 or 5 the board refrains from auto detection and imposes the specific
interface and speed.
T. UpsAddr
Syntax:
GE> T
Enter IP of host to ping:
X.X.X.X [Enter]
Description:
Ping the corresponding address TCP/IP.
U. Trap
Config
Syntax:
GE>U
RFC traps (sent always from ups 0) (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 0 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 1 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 2 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 3 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 4 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 5 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 6 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 7 (0 = off 1 = on) [0] :
X
[Enter]
GE Traps sent from ups 8 (0 = off 1 = on) [0] :
X
[Enter]
Default:
all traps disabled
Description:
Enabled/Disabled the sent of trap for a specified UPS.
V. Responsible
Syntax:
GE>V
Enter responsible e-mail : [[email protected]]:
XYZ
[Enter]
Default:
Description:
The e-mail address of the responsible person for this agent.