beautypg.com

1 bell alarm with lockout – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac Maintenance Manual User Manual

Page 48

background image

EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 8. Accessory Maintenance

38

This section describes the removal, replacement, and

adjustment of the various accessories available with

EntelliGuard breakers.
Before any of the operations in this chapter can be per-

formed, the breaker must be removed from its compart-

ment, as described in Section 5.2, and placed on a suitable

work surface.

8.1 Bell Alarm with Lockout

The Bell Alarm with Lockout locks out the breaker in the

event of a protection trip. The device has one normally

open output switch and a trip circuit that are connected to

the secondary disconnect as illustrated in Figure 43. The

switch output provides status feedback to the EntelliGuard

Messenger. The Bell Alarm with Lockout can only be reset

manually by pressing the yellow target/RESET button on

the breaker escutcheon.
Renewal parts for the Bell Alarm with Lockout are a

complete kit including mounting hardware, illustrated in

Figure 44, or the module only.

Removing the Bell Alarm with Lockout

Use the following procedure to remove the Bell Alarm

with Lockout module and mounting plate, as illustrated in

Figure 45. If only the Bell Alarm module is to be replaced,

it is not necessary to remove the mounting plate (perform

steps 1–3 only).

1. Remove the breaker escutcheon, as described in

Section 7.5.

2. Remove the four Bell Alarm wires from the

secondary disconnect, as listed in Table 6. Cut the

wire ties securing the wire bundle to the breaker

frame so that the four wires can be removed with

the Bell Alarm.

3. Remove the two screws and bushings securing the

Bell Alarm module to the mounting plate and

remove the module.

4. Remove the three nuts and lock washers securing

the mounting plate to the breaker frame.

5. Disengage the mounting plate from the breaker

mechanism and remove the plate.





Figure 43. Bell Alarm with Lockout connections to the secondary

disconnect. The contact is shown in the RESET state.

Figure 44. Bell alarm with Lockout accessory kit.

Figure 45. Bell Alarm with Lockout installation or removal.

14

2

1

Lockout

Trip Coil

6

16

4

3

Status

Contact

19