1 operating instructions – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac Maintenance Manual User Manual
Page 17

EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 4. Breaker Operation
7
4.1 Operating Instructions
Sequence of Operations
The sequence of operations that may be performed on the
circuit breaker are listed in Table 3.
Operation of the Breaker
Manually Charging the Closing Springs
Pull the operating handle down about 90° (until it stops)
six times to fully charge the closing springs. This will
not close the breaker contacts
. The charge indicator will
show
CHARGED
on a yellow background.
NOTE: The breaker cannot be closed unless
the springs are fully charged and the handle is
stored fully in.
NOTE: Le disjoncteur ne peut être fermé à
moins que les ressorts ne soient pleinement
chargés et que la poignée ne soit pleinement
rentrée.
Electrically Charging the Closing Springs
If the breaker is equipped with the (optional) Charging
Motor, the closing springs may also be charged with any
the following methods:
• With the breaker in the
TEST
position, install the
motor fuse in the fuse holder in the upper left corner
of the breaker compartment.
• Operate the Charging Motor by applying the rated
voltage to secondary disconnect terminals 8 and 17.
Power to the motor is removed automatically by a
cutoff switch when the springs are fully charged.
• If power is lost during the charging cycle, finish
charging the springs by cycling the charging handle
until the indicator shows
CHARGED
on a yellow
background.
The closing springs will automatically recharge after
closing if control power is maintained at terminals 8 and
17.
Closing the Breaker
Close the breaker contacts with any of the following
methods:
• Depress the
CLOSE
button on the front of the
breaker.
• Close the breaker using the Entellisys™ HMI.
• Energize the (optional) Remote Close accessory by
applying the rated voltage to secondary disconnect
terminals 9 and 18.
If the breaker is closed electrically and the closing voltage
is maintained, an antipump device prevents a second clos-
ing operation on the breaker in the event it is tripped
OPEN
. The closing impulse must be released for 1 to 2.5
seconds and reapplied before a second closing operation
can occur.
If the closing voltage is applied while the closing springs
are not fully charged, the Remote Close coil energizes, but
operation of the closing mechanism is blocked. The
closing voltage must be removed and reapplied when the
springs are fully charged to close the breaker.
A mechanical interlock prevents the closing springs from
discharging if an attempt is made to close an already
CLOSED
breaker.
NOTE: The main breaker contacts cannot be
closed if any of the following conditions apply:
• The draw-out mechanism is in any posi-
tion other than
TEST
or
CONN
, as dis-
played on the breaker position indicator.
• The (optional) Bell Alarm with Lockout
was not reset after an overcurrent lockout.
• The (optional) Open Fuse Lockout was
not reset after replacement of a blown fuse.
• The (optional) Network Interlock was not
reset after a set operation.
These conditions must be corrected before the
breaker can be closed. Attempts to close the
breaker before these conditions are corrected
may result in discharge of the closing springs
without closing the main contacts.
Open/Closed
Indicator
Main Breaker
Contacts
Charge
Indicator
Condition of Close
Springs
Next Permissible
Operating Function
OPEN
Open
DISCHARGED
Discharged
Mechanism may be charged
OPEN
Open
CHARGED
Charged
Contacts may be closed
CLOSED
Closed
DISCHARGED
Discharged
Mechanism may be recharged or
Contacts may be opened
CLOSED
Closed
CHARGED
Charged
Contacts may be opened
Table 3. Sequence of operations that may be performed with the EntelliGuard circuit breaker