beautypg.com

1 primary disconnects – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac Maintenance Manual User Manual

Page 38

background image

EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 7. Maintenance of Standard Parts and Assemblies

28

This section describes procedures for replacing the stan-

dard parts and assemblies available as renewal parts.
Before any of the operations in this chapter can be per-

formed, the breaker must be removed from its compart-

ment, as described in Section 5.2, and placed on a suitable

work surface.

7.1 Primary Disconnects

Primary disconnects provide the flexible connection

between the breaker line and load terminals and the

equipment line and load terminals.
Primary disconnect assemblies are different between the

EGS08, EGF08, and EGH08 frames, as illustrated in Figure

25, and the EGX08, EGS16, EGF16, EGH16, EGS20, and

EGF20 frames, as illustrated in Figure 26. The procedures

for removal and installation of the two types are described

below.

Primary Disconnect Replacement on EGS08,

EGF08, and EGH08 Breakers

The following procedure is illustrated in Figure 27.
To remove a primary disconnect assembly, squeeze the

disconnect fingers together with a suitable tool until the

assembly releases from the stud, then slide it off.
To install a primary disconnect assembly, squeeze the dis-

connect fingers together with a suitable tool, slide the

assembly over the stud, then reduce the pressure on the

fingers until they close into the slots on the stud.

Primary Disconnect Removal on EGX08,

EGS16, EGF16, EGH16, EGS20, and EGF20

Breakers

The following procedure is illustrated in Figure 28.

1. Remove the two nuts from one of the long bolts

holding the primary disconnect assembly together.

2. Carefully slide out the bolt while removing the flat

washer, spring, bushing, upper retainer, bow-tie

spacers, and disconnect fingers from the top and

the bow-tie spacers, lower retainer, and fingers from

the bottom of the assembly.

3. Repeat for the other assembly bolt and components.
4. Slide off the spring clips and remove the two stud

spacers.

5. Remove the main retainer from the stud.

Figure 25. Primary disconnect assembly for EGS08, EGF08, and EGH08

breakers.

Figure 26. Primary disconnect assembly for EGX08, EGS16, EGF16,

EGH16, EGS20, and EGF20 breakers.