beautypg.com

GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac Maintenance Manual User Manual

Page 26

background image

EntelliGuard™ 800–2000 A Power Circuit Breakers
Chapter 5. Breaker Maintenance

16

Separation of Front and Back Frames for

EGX08, EGS16, EGF16, EGH16, EGS20, and

EGF20

The following procedure is illustrated in Figure 10.

1. Verify that the breaker contacts are open and that

the closing springs are discharged.

2. Remove the two bolts and lock washers that attach

the arc chute retainer to the front frame and

remove the retainer. Slide out the arc chutes and

interphase barriers. Note that there are three dis-

tinct types of phase barriers: right, inner (2), and

left.

3. Remove the two screws and standoffs securing each

secondary disconnect to the mounting plate, taking

care to retain the spring washer from the pin on the

underside of the disconnect, as illustrated in Figure

6. Cut the wire ties securing the secondary discon-

nect leads to the mounting plate and to the breaker

back frame. Slide the secondary disconnect off the

support bracket. Secure the secondary disconnect to

the front frame assembly.

4. Remove the three screws and washers that attach

the secondary disconnect mounting plate to the

back frame. Remove the mounting plate.

5. Remove one of the snap rings and slide out the pin

connecting each of the movable contact assemblies

to the breaker main shaft, as illustrated in Figure 9.

On the two outer poles, first remove the bolt and

cover over the outer end of the pin.

6. Carefully place the breaker on its back, resting on

the primary disconnects.

7. Remove the two nuts and lock washers attaching the

tie bars to the front frame.

8. Remove the six nuts and lock washers (the top con-

nections also have spacers) connecting the front

and back frames.

9. Lift the front frame straight off the back frame.

Reconnection of Front and Back Frames for

EGX08, EGS16, EGF16, EGH16, EGS20, and

EGF20

The following procedure is illustrated in Figure 10.

1. Carefully place the back frame on a suitable work

surface, resting on the primary disconnects.

2. Carefully lower the front frame onto the back frame,

lining up the six studs in the sides of the back frame

with the corresponding holes in the front frame.

Attach the six nuts and lock washers, with the two

spacers on the top studs, and tighten to 250 in-lb.

Figure 9. Movable contact connection to the breaker main shaft on

EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20 breakers.

3. Attach the two nuts and lock washers to secure the

tie bars to the front frame. Tighten to 250 in-lb.

4. Carefully place the breaker upright, resting on its

bottom surface.

5. Reconnect the movable contact assemblies to the

breaker main shaft by inserting the connecting pin

and reattaching the snap ring, as illustrated in

Figure 9. Reattach the cover and bolt on the two

outer poles.

6. Reattach the secondary disconnect mounting plate

with three screws and washers to the back frame.

7. Place the flexible washer on the molded pin on the

bottom of the secondary disconnect, then slide the

two feet into the slots on the mounting plate. Secure

with the two screws and standoffs, as illustrated in

Figure 6. Replace the wire bundle into the channel

on the top of the frame and secure with wire ties.

8. Insert the four interphase barriers into position,

noting the proper locations for the three different

types.

9. Slide the arc chutes into position. Place the arc

chute retainer in position and secure with the two

bolts and lock washers to the front frame. Tighten

securely.

10. Check that no wires are interfering with breaker

operation and that all bolts and nuts are tight.

Operate the breaker a few times to verify proper

operation.