property. For example, if “Decimal”=2 and the register value is 14561, it will be displayed as
14561

Project data

This option means that the data read from the register will be converted to project data

before being displayed. The conversion is done following the formula below:

The Converted Data= (original register data – Min Input) * (Eng. Max – Eng. Min) /

(Max Input – Min Input)

Users can use project data in such conditions, for example:
AD real input is 0-1023. But users want to show the data as 0-10V.
Calculate the new data which according to the input of project data.Then modify the

value of corresponding register inside the PLC to the new data. Etc.
Example: Users should set 0-10V to correspond with the AD inputting register D0(0-1023).
Set as below:

When user set 10, the value of D0 is 1023.
When user set 0, the value of D0 is 0.
The value of D0 (original register data – Min Input) * (Eng. Max – Eng. Min) / (Max Input –
Min Input)