Installation guide, Supported system types, H84xx – Veris Industries H84xx Install User Manual
Page 5

Z204046-0J
PAGE 5
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
12115
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H84xx
INSTALLATION GUIDE
SUPPORTED SYSTEM TYPES
Voltages Less Than or Equal to 347VAC L-N/600VAC L-L, Direct Connect, No PTs
CTs
Voltage Connections
Meter Configuration
Number of
wires
Qty ID
Qty
ID
Type
System Type
PT Primary
Scale
Figure
Number
SIngle-Phase Wiring
2
1
I1
2
V1, Vn
L-N
10
No PT
12
2
1
I1
2
V1, V2
L-L
11
No PT
13
3
2
I1, I2
3
V1, V2, Vn
L-L with N
12
No PT
14
Three-Phase Wiring
3
3
I1, I2, I3 3
V1, V2, V3
Delta
31
No PT
15
3
1
I1
3
V1, V2, V3
Delta (balanced)
32
No PT
16
4
3
I1, I2, I3 3
V1, V2, V3, Vn 4-Wire Delta
40
No PT
17
4
3
I1, I2, I3 3
V1, V2, V3, Vn Wye
40
No PT
17
4
1
I1
3
V1, V2, V3, Vn Wye (balanced)
44
No PT
23
Voltages Greater Than 347VAC L-N/600VAC L-L
CTs
Voltage Connections
Meter Configuration
Number of
wires
Qty ID
Qty
ID
Type
System Type
PT Primary
Scale
Figure
Number
Three-Phase Wiring
3
3
I1, I2, I3 2
V1, V3 (V2 to
ground)
Delta
31
Based on
voltage
18
3
1
I1
2
V1, V2, V3 (Vn
to ground)
Delta (balanced)
32
Based on
voltage
19
4
3
I1, I2, I3 3
V1, V2, V3 (Vn
to ground)
Grounded Wye
40
Based on
voltage
20
3
I1, I2, I3 2
V1, V2, V3 (Vn
to ground)
Wye
42
Based on
voltage
21
4
1
I1
3
V1, V2, V3 (Vn
to ground)
Grounded Wye
(balanced)
44
Based on
voltage
22