Z204046-0J

PAGE 5

©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

12115

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

H84xx

INSTALLATION GUIDE

SUPPORTED SYSTEM TYPES

Voltages Less Than or Equal to 347VAC L-N/600VAC L-L, Direct Connect, No PTs

CTs

Voltage Connections

Meter Configuration

Number of

wires

Qty ID

Qty

ID

Type

System Type

PT Primary

Scale

Figure

Number

SIngle-Phase Wiring
2

1

I1

2

V1, Vn

L-N

10

No PT

12

2

1

I1

2

V1, V2

L-L

11

No PT

13

3

2

I1, I2

3

V1, V2, Vn

L-L with N

12

No PT

14

Three-Phase Wiring
3

3

I1, I2, I3 3

V1, V2, V3

Delta

31

No PT

15

3

1

I1

3

V1, V2, V3

Delta (balanced)

32

No PT

16

4

3

I1, I2, I3 3

V1, V2, V3, Vn 4-Wire Delta

40

No PT

17

4

3

I1, I2, I3 3

V1, V2, V3, Vn Wye

40

No PT

17

4

1

I1

3

V1, V2, V3, Vn Wye (balanced)

44

No PT

23

Voltages Greater Than 347VAC L-N/600VAC L-L

CTs

Voltage Connections

Meter Configuration

Number of

wires

Qty ID

Qty

ID

Type

System Type

PT Primary

Scale

Figure

Number

Three-Phase Wiring
3

3

I1, I2, I3 2

V1, V3 (V2 to

ground)

Delta

31

Based on

voltage

18

3

1

I1

2

V1, V2, V3 (Vn

to ground)

Delta (balanced)

32

Based on

voltage

19

4

3

I1, I2, I3 3

V1, V2, V3 (Vn

to ground)

Grounded Wye

40

Based on

voltage

20

3

I1, I2, I3 2

V1, V2, V3 (Vn

to ground)

Wye

42

Based on

voltage

21

4

1

I1

3

V1, V2, V3 (Vn

to ground)

Grounded Wye

(balanced)

44

Based on

voltage

22