H84xx
INSTALLATION GUIDE
<-
PULSE SETUP
1;
+
OK
100
0.1
100
0.1
KWH/P
MSEC
KVARH
&
MSEC
<-
COMMS SETUP
1;
+
OK
9600
nOnE
bauD
Par
mbus
ADDR
001
<-
DEMAND SETUP
1;
+
OK
100
15
1
0.1
MIN
SUB-i
KVARH
&
MSEC
I
<-
PULSE SETUP
1;
+
OK
100
0.1
_ _
KWH/P
PHASE
&
MSEC
Set Up Demand
1. Press -----> until DEMND (demand) is visible. (H8437V/VB/S only)
2. Press DEMND.
3. Enter the MIN (interval in minutes): 0 to 60. Press + to change a digit, <----- to
select the next digit.
4. Press OK. Enter the SUB-I (number of subintervals): 1 to 60. Press + to change a
digit, <----- to select the next digit.
5. Press OK.
NOTE: The calculation method used for SUB-I is as follows:
• 0 = sliding block
• 1 = block
• >1 = rolling block (The SUB-I value must divide evenly into the MIN
value. For example, if MIN is 15, SUB-I can be 3, 5, or 15. If you selected 3,
you would have 3 subintervals at 5 minutes each.)
Set Up Communications (H8436V/VB, H8437V/VB)
1. Press -----> until COM is visible.
2. Press COM.
3. Enter the ADDR (meter address): 1 to 247. Press + to change a digit, <----- to
select the next digit.
4. Press OK.
5. Press + to select the BAUD (baud rate): 2400, 4800, 9600 or 19200.
6. Press OK.
7. Press + to select the parity: EVEN, ODD, NONE.
8. Press OK to return to the SETUP MODE screen.
Set Up Pulse Options (H8453V/VB, H8463V/VB)
1. Press -----> until PULSE is visible.
2. Press PULSE.
3. Press + to select the MSEC (kWh pulse duration in milliseconds): 100, 300, 500, or
1000.
4. Press OK.
5. Press + to select the kWh/P (pulse weight): 0.1, 1, 10, 100, 1000, or 10000.
6. Press OK.
7. Select the MSEC (kVARh pulse
duration in milliseconds): PHASE, 100,
300, 500, or 1000.
NOTE: Selecting PHASE changes the output operation from kVARh to PHASE DETECT.
If phase is selected, the H8453V/VB will close the contacts on the PHASE kVARh
output when all three phase voltages are within 25% of each other and no phase
is less than 82.5 volts Line to Neutral. The H8463V/VB will open the contacts on
the Phase kVARh output when all three phase voltages are within 25% of each
other and no phase is less than 82.5 volts line to neutral.
8. Press OK.
9. Select the kVARh (pulse weight):
0.1, 1, 10, 100, 1000, or 10000. This
is unavailable if PHASE is selected
above.
10. Press OK to return to the SETUP
MODE screen.