9600 none, Installation guide – Veris Industries H84xx Install User Manual

Page 15

background image

Z204046-0J

PAGE 15

©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

12115

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

H84xx

INSTALLATION GUIDE

<-

PULSE SETUP

1;

+

OK

100

0.1

100

0.1

KWH/P

MSEC

KVARH

&

MSEC

<-

COMMS SETUP

1;

+

OK

9600

nOnE

bauD

Par

mbus

ADDR

001

<-

DEMAND SETUP

1;

+

OK

100

15

1

0.1

MIN

SUB-i

KVARH

&

MSEC

I

<-

PULSE SETUP

1;

+

OK

100

0.1

_ _

KWH/P

PHASE

&

MSEC

Set Up Demand

1. Press -----> until DEMND (demand) is visible. (H8437V/VB/S only)

2. Press DEMND.

3. Enter the MIN (interval in minutes): 0 to 60. Press + to change a digit, <----- to

select the next digit.

4. Press OK. Enter the SUB-I (number of subintervals): 1 to 60. Press + to change a

digit, <----- to select the next digit.

5. Press OK.

NOTE: The calculation method used for SUB-I is as follows:

• 0 = sliding block
• 1 = block
• >1 = rolling block (The SUB-I value must divide evenly into the MIN

value. For example, if MIN is 15, SUB-I can be 3, 5, or 15. If you selected 3,
you would have 3 subintervals at 5 minutes each.)

Set Up Communications (H8436V/VB, H8437V/VB)

1. Press -----> until COM is visible.

2. Press COM.

3. Enter the ADDR (meter address): 1 to 247. Press + to change a digit, <----- to

select the next digit.

4. Press OK.

5. Press + to select the BAUD (baud rate): 2400, 4800, 9600 or 19200.

6. Press OK.

7. Press + to select the parity: EVEN, ODD, NONE.

8. Press OK to return to the SETUP MODE screen.

Set Up Pulse Options (H8453V/VB, H8463V/VB)

1. Press -----> until PULSE is visible.

2. Press PULSE.

3. Press + to select the MSEC (kWh pulse duration in milliseconds): 100, 300, 500, or

1000.

4. Press OK.

5. Press + to select the kWh/P (pulse weight): 0.1, 1, 10, 100, 1000, or 10000.

6. Press OK.

7. Select the MSEC (kVARh pulse
duration in milliseconds): PHASE, 100,
300, 500, or 1000.

NOTE: Selecting PHASE changes the output operation from kVARh to PHASE DETECT.

If phase is selected, the H8453V/VB will close the contacts on the PHASE kVARh
output when all three phase voltages are within 25% of each other and no phase
is less than 82.5 volts Line to Neutral. The H8463V/VB will open the contacts on
the Phase kVARh output when all three phase voltages are within 25% of each
other and no phase is less than 82.5 volts line to neutral.

8. Press OK.

9. Select the kVARh (pulse weight):

0.1, 1, 10, 100, 1000, or 10000. This
is unavailable if PHASE is selected
above.

10. Press OK to return to the SETUP

MODE screen.