beautypg.com

Figure 10, Electrical connection for dil-1/h – M&C TechGroup DIL-1_(H) Operator's manual User Manual

Page 21

background image

21

Gas sampling and gas conditioning technology

2-1.1.7.6-ME

N O T E !

For the erection of power installations with nominal voltages of up
to 1000V, the requirements of VDE 0100 and its associated stan-
dards and specifications must be observed.
A main switch must be provided externally.
The supply circuit of the unit must be equipped with a fuse with the
correct rating (over current protection); the electrical details see
technical data.

Remove cover of the connection box.

Insert the mains cable (min. 3 x 1,5 mm

2

) through the cable gland and connect to the appropriate

terminals.

Insert the signal cable (low temperature alarm) through the cable gland and connect to the appro-
priate terminals (contact position T

u

shows alarm event).

Screw cover back in place.

Mains 230V 50Hz
or 115V 60Hz

Alarm outlet

1

2

1

2

+30

-30

800 W

Figure 10

Electrical connection for DIL-1/H..

W A R N I N G !

We recommend the use of temperature resistent cables!