G8000 Series Installation and operation Manual

14.5 Stop

The procedure to stop the UpS is shown in Steps 1-3.

STEP 1

Transfer to bypass supply as described in

Switch Power Supply.
UpS leD is “oFF”.
bypASS leD is “on”.

STEP 2

Turn off the DC Input breaker (72b) on

the external battery cabinet, and, press

the G8000 “STop” button for at least 0.5

seconds.
bATTerIeS leD is “oFF”.
INVERTER LED flashes then “OFF”.
FloAT CHArGe leD and ConVerTer

leD are “oFF”.

STEP 3

wait until procedure is completed.

CONVERTER

INVERTER

UPS

AC OUTPUT

BATTERIES

BYPASS INPUT

DISCHARGE

EQUAL CHARGE

FLOAT CHARGE

BYPASS

AC INPUT

AC

SWITCH

BYPASS

AC - Vo 480 V

AC - Io 50%

PRESS ‘UPS’ SWITCH

CONVERTER

INVERTER

UPS

AC OUTPUT

BATTERIES

BYPASS INPUT

DISCHARGE

EQUAL CHARGE

FLOAT CHARGE

BYPASS

AC INPUT

AC

SWITCH

BYPASS

MOVE #72B TO ‘OFF’ POSITION

CONVERTER

INVERTER

UPS

AC OUTPUT

BATTERIES

BYPASS INPUT

DISCHARGE

EQUAL CHARGE

FLOAT CHARGE

BYPASS

AC INPUT

AC

SWITCH

BYPASS

PRESS ‘RUN’ SWITCH

LED Key

- LED Off

- LED On

- LED Flash