14.1 Operation Types

The operation types are summarized below.

TABLE 14.1 OPERATION TYPES

Operation

Description

Complete Shutdown

Turn off the control power supply. Shut down the UpS

completely.

Float / equalize Charge Changing the battery recharge mode between float charge and

equalize charge.

protection Charge

Automatic recharge mode transition from protection charge to

float charge.

Startup

Starting up and operating the UpS.

Stop

Stop the inverter and chopper/charger.

Switch power Supply

Switching power supply source between UpS and bypass.

14.2 Pre-operational Check

before operating the UpS:

1. Make sure all covers/panels are in place and secured.

2. Make sure the temperature in the UPS/Battery room is within specified limits.

3. before starting the UpS, check the power source to make sure AC input power is on.
4. Make sure battery breaker’s auxiliary A-contact is connected to the terminal block Tb1.

CAUTION

Perform the pre-operational check before operating the UPS.