beautypg.com

Step 4, Step 5, Step 4-5 continues the procedure to start the ups – Toshiba G8000 User Manual

Page 65: Bypass move 72b to ‘on’ position

background image

57

G8000 Series Installation and operation Manual

Step 4-5 continues the procedure to start the UpS.

STEP 4

Turn on the DC Input breaker (72b) on the

external battery cabinet.
bATTerIeS leD is “on”.

STEP 5

*press the “UpS” button for at least 0.5

seconds. This completes UpS startup

procedure
bypASS leD is “oFF”.
UpS leD is “on”.

NOTE
*

If the AC switch does not function, contact

Toshiba or authorized representatives.
If the bypass power source is out of

specification, this operation will be inhibited.

In order to switch manually, press the “UpS”

button for 5 seconds or more.

CONVERTER

INVERTER

UPS

AC OUTPUT

BATTERIES

BYPASS INPUT

DISCHARGE

EQUAL CHARGE

FLOAT CHARGE

BYPASS

AC INPUT

AC

SWITCH

BYPASS

MOVE 72B TO ‘ON’ POSITION

CONVERTER

INVERTER

UPS

AC OUTPUT

BATTERIES

BYPASS INPUT

DISCHARGE

EQUAL CHARGE

FLOAT CHARGE

BYPASS

AC INPUT

AC

SWITCH

UPS SUPPLY

AC - Vo 480 V

AC - Io 50%

LED Key

- LED Off

- LED On

- LED Flash