51

G8000 Series Installation and operation Manual

TABLE 13.2 - CONTINUED

MEASUREMENT SCREENS

O/P CURRENT (PEAK)

Shows the peak output current peak (%) for each phase.

U 50[%]

V 50[%]

W 50[%]

peak value of output current

x 100 [%]

rMS value for rated current x 1.41

AC INPUT

Shows the AC Input Voltage (line-to-line) and frequency.

AC I/P-V 480[V]

FREQ. 60.0[Hz]

BYPASS INPUT

Shows the bypass Input Voltage (line-to-line voltage) and

frequency.

BYP I/P-V 480[V]

FREQ. 60.0[Hz]

BATTERY

Shows the remaining battery backup time with rated load

and cumulative discharged time.

BACK-UP RATING 10[MIN]

DISCHARGING 15[MIN]

DC INPUT

Shows the internal DC bus voltage, battery voltage and

battery current.
The battery current value displayed is negative during

recharge and positive during discharge.

DC-V 632[V]

BATT-V 400[V]

BATT- I 0[A]

MODE COUNT

Shows the cumulative UpS operation time, the

cumulative battery backup time and the number of battery

backup operations.

UPS 35[H]

BATTERY 56[MIN]

32[TIM]

CLOCK

The current time is displayed if there are no faults

recorded, or after the reset button is pressed.
Date is displayed in the mm-ddyyy format. The unit does

not calculate daylight savings time.
Time is displayed in the 24-hour format (e.g. 1:58 p.M. =

1358 Hrs.)

TIME 03-24-06 13:58