G8000 Series Installation and operation Manual

11.2 150, 225, and 300 kVA Buss Strip Terminals and Power Cables

Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and

circuit protection device requirements.

The 150, 225, and 300 kVA UpS units have buss strip power terminals. Figure 11.3 is a typical buss strip

for a 150/225 kVA UpS.

FIGURE 11.3 - TERMINAL BUS DETAIL

Figure 11.4 shows the arrangement of the terminal buss strips for the 150 and 225 kVA UpS units. The

terminal buss strips are located inside, at the bottom of the UpS. The dashed line indicates the side

view of the bolt holes. Use 1/2 inch bolts to attach the lugs.

FIGURE 11.4 - TERMINAL BUSS ARRANGEMENT FOR 150 AND 225 KVA UPS

Figure 11.5 shows the arrangement of the terminal buss strips for the 300 kVA UpS. The buss strips are

located inside at the top of the unit.

FIGURE 11.5 - TERMINAL BUSS ARRANGEMENT FOR 300 KVA UPS

3

w

4

U

5

V

6

w

7

n

8

U

9

V

12

10

w

2

V

1

U

11

n

13

+

AC InpUT

AC oUTpUT

bypASS InpUT

bATTery

9

n

1

U

3

w

2

V

AC InpUT

3-phase 3-wire

4

5

+

bATTery

6

U

8

w

7

V

bypASS InpUT

3-phase 4-wire

12

w

10

U

11

V

AC oUTpUT

3-phase 4-wire

5.3 in. (135 mm)

1.97 in.

(50 mm)

1.77 in.

(45 mm)

1.75 in.

(45 mm)

3 in.

(77 mm)

0.5 in. Dia.

(1.27 mm)