12 ups specifications, 1 general specification, 2 mechanical specification – Toshiba G8000 User Manual
Page 51

43
G8000 Series Installation and operation Manual
12 UPS Specifications
12.1 General Specification
Terms
Specification
remarks
Conforming Standard
Ul1778-2001
Ul, cUl
Ambient Temperature
pF = 1.0: 32
– 86 °F (0 – 30 °C)
pF = 0.8: 86
– 104 °F (30 – 40 °C)
relative Humidity
30% – 90%
non-condensing
Altitude
< 3,280 ft. (< 1,000 m)
Contact Toshiba Technical
Support for installation above
3280 ft. (1000 m)
Audible noise
68 db (100/150/225 kVA), 72 db (300 kVA)
39 in. (1m) away from front
Insulation resistance
3 MΩ
with 500V-Megger
Insulation breakdown
AC 2 kV – 1 min.
Main Circuit
AC 1.5 kV – 1 min.
external Interface
AC 500 V – 1 min.
Control Circuit
12.2 Mechanical Specification
nominal Capacity
100
kW:
T80S3K10KK6XS
2H
Cabinet protection
Conformity
IeC298 Ip20*
exterior paint
Sherwin williams, HHT2-7055, 079 beige Texture
panel Thickness
FronT: 1.6 mm (1/16 in.)
bACK/SIDe/Top: 1.2 mm (3/64 in.)
boTToM: 3.2 mm (1/8 in.)
Input/output
Cabling entrance
boTToM
Ground/Control
wiring entrance
boTToM
outline Dimension
w: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
Unit weight
1740 lb. (789 kg)
Shipping weight
1790 lb. (812 kg)
Floor loading per
Footprint
2180 lb./ft.
2
(10,644 kg/m
2
)
Clearance
FronT: 43 7/16 in. (1100 mm)
bACK/SIDe: 0 in. (0 mm)
Top: 15 3/4 in. (400 mm)
Heat rejection
34,121 bTU/h
(8598 kcal/h)
*Ip20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UpS.