beautypg.com

12 ups specifications, 1 general specification, 2 mechanical specification – Toshiba G8000 User Manual

Page 51

background image

43

G8000 Series Installation and operation Manual

12 UPS Specifications

12.1 General Specification

Terms

Specification

remarks

Conforming Standard

Ul1778-2001

Ul, cUl

Ambient Temperature

pF = 1.0: 32

– 86 °F (0 – 30 °C)

pF = 0.8: 86

– 104 °F (30 – 40 °C)

relative Humidity

30% – 90%

non-condensing

Altitude

< 3,280 ft. (< 1,000 m)

Contact Toshiba Technical

Support for installation above

3280 ft. (1000 m)

Audible noise

68 db (100/150/225 kVA), 72 db (300 kVA)

39 in. (1m) away from front

Insulation resistance

3 MΩ

with 500V-Megger

Insulation breakdown

AC 2 kV – 1 min.

Main Circuit

AC 1.5 kV – 1 min.

external Interface

AC 500 V – 1 min.

Control Circuit

12.2 Mechanical Specification

nominal Capacity

100

kW:

T80S3K10KK6XS

2H

Cabinet protection

Conformity

IeC298 Ip20*

exterior paint

Sherwin williams, HHT2-7055, 079 beige Texture

panel Thickness

FronT: 1.6 mm (1/16 in.)

bACK/SIDe/Top: 1.2 mm (3/64 in.)

boTToM: 3.2 mm (1/8 in.)

Input/output

Cabling entrance

boTToM

Ground/Control

wiring entrance

boTToM

outline Dimension

w: 36.8 in. (935 mm)

D: 31.8 in. (808 mm)

H: 79.2 in. (2012 mm)

Unit weight

1740 lb. (789 kg)

Shipping weight

1790 lb. (812 kg)

Floor loading per

Footprint

2180 lb./ft.

2

(10,644 kg/m

2

)

Clearance

FronT: 43 7/16 in. (1100 mm)

bACK/SIDe: 0 in. (0 mm)

Top: 15 3/4 in. (400 mm)

Heat rejection

34,121 bTU/h

(8598 kcal/h)

*Ip20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UpS.