G8000 Series Installation and operation Manual

WARNING

While operating in the inverter mode, placing the input breaker

in the “OFF” position will switch the UPS to the battery backup

mode.
The output of the UpS will continue uninterrupted to the load. The unit

must be in the bypass mode at the time that the breaker is placed in

the “oFF” position for the UpS to shutdown power to the load.

CAUTION

After an Emergency Power Off (EPO), DO NOT reset the breaker

until the UPS internal circuits have been fully discharged.
The UpS could be damaged if the unit is not fully discharged before

the breaker is reset.

3) The UpS should not be used with a load that has a rated input that is greater than the

rated output of the UpS.

4) If using the UpS to provide power to motors that require high starting current or with

motors that require a long starting time, call Toshiba support for guidance in over

sizing the UpS for lock rotor current.

5) Do noT insert metal objects or combustible materials in the ventilation slots of the

UpS.

6) Do noT place, hang, or paste any objects on the exterior surfaces of the UpS.
7) The capacitors in the UpS maintain a residual charge for a while after turning the UpS

off. The required discharge time for each UpS typeform is provided via a cabinet label

and a

CHARGE LED. wait for at least the minimum time indicated on the label and

ensure that the

CHARGE LED has gone out before opening the door of the UpS once

the UpS power has been turned off.

8) Do noT attempt to disassemble, modify, or repair the UpS. Call your Toshiba sales

representative for repair information.

9) Turn the power on only after installing

ALL of the covers.

10) Do noT remove any covers of the UpS when power is on.
11) If the UpS should emit smoke or an unusual odor or sound, turn the power off

immediately.

12) Warning signs should be placed on or near the load as a notification that the load is

being powered by the UpS.

13) Additional warnings and notifications shall be posted at the equipment installation

location as deemed required by

Qualified Personnel.