TABLE 5.1 - UPS INSTALLATION ENVIRONMENT STANDARDS

Item

environment standard

Installation location Indoors

Ambient

Temperature

Minimum operating temperature: 32

°F (

0

°

C).

Maximum operating temperature: 86

°F

(30

°

C) at 1.0 pF (UpS with/without

battery system).
Maximum operating temperature: 90

°F

(32

°

C) at 0.8 pF (UpS with battery

system).
Maximum operating temperature: 104

°F (

40

°

C) at 0.8 pF (UpS only).

Average 24-hour operating temperature: 86

°F

(30

°

C) at 1.0 pF and 41

– 95 °F

(

5

35

°

C) at 0.8 pF.

relative Humidity

The relative humidity must be between 30 and 90% noncondensing due to

temperature changes.

Altitude

These specifications are for altitudes up to 3240 ft. (1000 m) above sea level.

Consult with the factory to determine the derating factor for installations above

3240 ft. (1000 m).

Vibration and

Mechanical Shock

Installation environment must not have vibration frequencies 10 Hz

20 Hz.

The acceleration due to vibrations less than 10 Hz must not exceed 0.5 G.
The acceleration due to vibrations 20 Hz

50 Hz must not exceed 0.5 G.

The total amplitude due to vibrations 50 Hz

100 Hz must not exceed 0.1 mm.

Dust

Dust must not exceed normal atmospheric levels and must not include conductive

particles, silicone or oils.

Flammable Gas

No flammable and/or explosive gas.
Hydrogen sulfide (H

2

S)

less than or equal to 0.0001 ppM

Sulfurous acid gas (So

2

)

less than or equal to 0.05 ppM

Chlorine gas (Cl

2

)

less than or equal to 0.002 ppM

Ammonia gas (nH

3

)

less than or equal to 0.1 ppM

nitrous acid gas (no

2

)

less than or equal to 0.02 ppM

nitrous oxides (nox)

less than or equal to 0.02 ppM

ozone (o

3

)

less than or equal to 0.002 ppM

Hydrochloric acid mist (HCl)

less than or equal to 0.1 mg/m

3

Installation Precautions

1) Install the unit in a stable, level and upright position that is free of excessive

vibration.

2) Install the unit where the ambient temperature is within the specified range.
3) Do noT install the UpS in areas that are subject to high humidity.
4) Do noT install the UpS in areas that allow exposure to direct sunlight.
5) Do noT install the UpS in areas that allow exposure to high levels of airborne dust,

metal particles, or flammable gases.

6) Do noT install the UpS in areas near sources of electrical noise. ensuring a proper

earth ground will reduce the effects of electrical noise and will reduce the potential for

electrical shock.