14

G8000 Series Installation and operation Manual

6 Warning Labels

below are representative warning labels and their location on the UpS. exterior Handling labels shown

in section 4.3, Transporting/Unpacking, are in the manual packet, and attached to the UpS shipping

covering and shipping pallet.

ATTENTION

Make sure all the warning labels are installed in the appropriate locations.
If a label is missing or illegible, contact Toshiba Customer Support Center or an

authorized representative.

DANGER

Hazardous voltages are used in the operation
of this equipment and could cause severe personal
injury or loss of life.
The following precautions should be observed to
reduce the risk of injury or death.

HAZARDOUS VOLTAGES

Only qualified technicians fam iliar with this equipment and the
information supplied with it s hould be permitted to install and
operate this equipment.

Ins tallation of electrical equipment must be done in
accordance with National Electrical Code and any other state
or local c odes. Proper grounding and conductor sizing must
be installed for safe operation.

During operation, keep all covers in place and cabinet
doors s hut.

When performing visual inspections and maintenance, if
possible, be sure the UPS is turned off and the incoming
AC feed is turned off and locked out.

If it is necessary to make measurements with the power
on, do not touch any electrical connection points. Remove
all jewelry from wrists and fingers. Make sure test equipment
is in good, safe operating condition.

While s ervicing, stand on some type of insulation, and be
sure not to be grounded.

Follow the safety instructions given in the equipment manual
carefully and observe all danger, warning and caution notices.

40308

The UPS and Battery Cabinet will have hazardous
voltages present even after the AC feed is turned off.

DANGER

AC VOLTAGE

This UPS receives power from more
than one source. Disconnect all AC
sources before performing any service
or testing inside this unit

48082

2

V

3

W

4

U

REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE

480 V

A C INPUT

480 V

BYPA SS INPUT

1

U

480V

AC OUTPUT

400 V

BATTERY

5

V

6

W

7

N

8

U

9

V

10

W

11

N

USE COPPER CONDUCTORS ONLY!

12

13

-

+

(B)

40308

(A)

48082

(C)

56875 FOR 100, 150, 225KVA

(C)

58708 FOR 300KVA

2

V

3

W

6

U

REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE

480 V

A C INPUT

480 V

BYPASS INPUT

1

U

480 V

AC OUTPUT

400 V

BATTERY

7

V

8

W

9

N

10

U

11

V

12

W

USE COPPER CONDUCTORS ONLY !

4

5

-

+

5

8

70

8

PN 40830

Incorrect fuse replacement size
may result in fire or inadequate
equipment protection.

Replace only with same type
and rating of fuse.

CRITICAL FUSE SIZING

WA R N I N G

(D)

40830

(E)

39561

DANGER

Turn off and lock out all power sources.
Wait at least five (5) minutes for power
to dissipate then check voltage before
servicing.

Capacitors stay c harged after power
has been s hut off.
Accidental contact with liv e parts can
cause personal injury and death.

RISK OF ELECTRIC SHOCK

39561

(F)

58705 SERIAL LABEL

®

LISTED

27E5

MFD. IN U.S .A. FR OM FOREIGN AND DOMES TIC C OMP ON ENTS

HOUS TON , TE XAS

58705

®

UNINTERRUPTIBLE POWER SUPPLY

(G)

57055

GND

(I)

40831

Risk of electrical shock.

PN 40831

Heat sink not grounded.

C A U T I O N

Disconnect UPS and electrically
test heat sink before touching.

(J)

57053

C A U T I O N

Do not turn off while operating.

8A

(control power source switch)