9.2 Maintenance Precautions

All internal maintenance sould be performed by factory authorized personnel.

1) Turn off, lockout, and tagout All power sources before connecting the power wiring to

the equipment or when performing maintenance.

2) Hardwire type UpS units are not equipped with an over-current protection device, nor

do they have an output disconnect for the AC output. A user-installed circuit breaker

should be provided between the UpS output and the load input.

3) The maximum ambient operating temperature is 86 °F (30 °C) at 1.0 pF, and 104 °F

(40 °C) at 0.8 pF.

4) only factory authorized personnel should service the UpS. Contact Toshiba for the

the nearest authorized service center.

5) battery servicing should be performed by factory authorized personnel only. Contact

your nearest factory authorized service center for battery replacement.

Qualified Personnel ONLY!
Qualified Personnel
have the skills and knowledge relating to the construction, installation, operation,

and maintenance of the electrical equipment and has received safety training on the hazards involved

(refer to the latest edition of nFpA 70e for additional safety requirements).

Qualified Personnel shall:

1) Have read the entire operation manual.
2) be trained and authorized to safely energize, de-energize, ground, lockout and

tag circuits and equipment, and clear faults in accordance with established safety

practices.

3) be trained in the proper use and care of protective equipment such as safety shoes,

rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance

with established safety practices.

4) Be trained in rendering first aid.
5) be knowledgeable of batteries and the required handling and maintenance

precautions.

For further information on workplace safety visit www.osha.gov.

WARNING

Misuse of equipment could result in injury and equipment damage.
In no event will Toshiba Corporation be responsible or liable for either

indirect or consequential damage or injury that may result from the

misuse of this equipment.