beautypg.com

9 storage/operating environment, 1 operating precautions – Toshiba G8000 User Manual

Page 30

background image

22

G8000 Series Installation and operation Manual

9 Storage/Operating Environment

observe the following when storing the UpS.

Store UpS indoors.

Maximum storage time for the UpS between powered operation cycles is three years.

If the UpS has been stored for a period exceeding 36 months, contact your factory

authorized represnetative of guidance in starting the unit.

Temperature fluctuations should be minimized.

The optimal storage temperature range is 68 – 77 °F (20 – 25° C).

A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.

The optimal relative humidity at the storage location should be between 50 – 60%.

Humidity must not exceed 90%.

Avoid locations where UpS may be exposed to corrosive gas.

Avoid locations with dirt and/or dust.

TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS

Item

environment standard

Storage location

Indoors

Ambient Temperature

Minimum storage temperature: 32 °F (0 °C)
Maximum storage temperature: 104 °F (40 °C)

relative Humidity

The relative humidity must be between 30 and 90% and without condensation

due to temperature changes.

Altitude

This equipment is rated for installations up to 3240 ft. (1000m) above

sea level. Consult with the factory to determine the derating factor for

installations above 3240 ft. (1000m).

Dust

Dust must not exceed normal atmospheric levels and must not include

conductive particles, silicone or oils.

Flammable Gas

No flammable and/or explosive gas.
Hydrogen sulfide (H

2

S)

less than or equal to 0.0001 ppM

Sulfurous acid gas (So

2

)

less than or equal to 0.05 ppM

Chlorine gas (Cl

2

)

less than or equal to 0.002 ppM

Ammonia gas (nH

3

)

less than or equal to 0.1 ppM

nitrous acid gas (no

2

)

less than or equal to 0.02 ppM

nitrous oxides (nox)

less than or equal to 0.02 ppM

ozone (o

3

)

less than or equal to 0.002 ppM

Hydrochloric acid mist (HCl)

less than or equal to 0.1 mg/m

3

9.1 Operating Precautions

Initial startup/comisioning of the UpS should be performed by factory authorized personnel.

1) The UpS should not be powered up until the entire operation manual has been

read.

2) The voltage of the input power source must be within the rated input voltage

range. The input frequency range must be within the rated input frequency

range.