beautypg.com

4 factory authorized personnel, 3 important safety instructions, Caution – Toshiba G8000 User Manual

Page 12

background image

4

G8000 Series Installation and operation Manual

Be trained in rendering first aid.

For further information on workplace safety visit www.osha.gov.

2.4 Factory Authorized Personnel

Factory authorized personnel have been factory trained and certified to install, service, and repair the

UpS. Contact the Toshiba Customer Support Center for assistance in locating the factory authorized

personnel nearest you.

3 Important Safety Instructions

The following contains important instructions that should be followed during the installation, operation,

and maintenance of the G8000 Series UpS.

please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or

replacing the batteries for each system. Keep unauthorized personnel from batteries. Only a certified

service representative with battery experience should perform service on batteries.

The UPS system input and output is NOT equipped with an over-current protection device, or an

output disconnection at the AC output. The user should provide circuit breakers between the UpS AC

input (or bypass input) and the power sources and between the UpS output and the critical load input.

The minimum device ratings are listed in Table 3.1.

The maximum operating ambient temperature is 86 °F (30 °C) at 1.0 pF, and 104 °F (40 °C) at 0.8 pF.

If the UpS is exposed to the same ambient temperature as the battery system, the maximum operating

ambient temperature is 86 °F (30 °C) at 1.0 pF, 90 °F (32 °C) at 0.8 pF. Table 3.2 lists the nominal battery

voltage.

TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE

C

apaCity

N

omiNal

V

oltage

F

loat

V

oltage

100 kVA

360 Vdc

405 V

150 kVA

360 Vdc

405 V

225 kVA

360 Vdc

405 V

300 kVA

360 Vdc

405 V

CAUTION

Misuse of this equipment could result in personal injury and/or equipment damage.

In no event will Toshiba Corporation be responsible or liable for either indirect or

consequential damage or injury that may come from the use of this equipment.

TABLE 3.1 UPS MINIMUM DEVICE RATINGS

C

apaCity

R

ated

o

utput

i

Nput

B

ReakeR

R

atiNg

o

utput

B

ReakeR

R

atiNg

100 kVA

480 V/277 V

480 V-200 A

480 V-150 A

150 kVA

480 V/277 V

480 V-300 A

480 V-225 A

225 kVA

480 V/277 V

480 V-450 A

480 V-350 A

300 kVA

480 V/277 V

480 V-500 A

480 V-450 A