Rcas_out (process), Rcas_out_d (process), Readback (scaling, tuning) – National Instruments NI-FBUS User Manual
Page 93: Readback_d (scaling, tuning), Reset (tuning), Restart (diagnostic, option), Table 4-19. restart values

Chapter 4
Parameters
NI-FBUS Configurator User Manual
4-28
ni.com
RCAS_OUT (Process)
The back calculation output used by the supervisory host when establishing
a Remote cascade loop.
RCAS_OUT_D (Process)
The discrete back calculation output used by the supervisory host when
establishing a Remote cascade loop.
READBACK (Scaling, Tuning)
The valve or actuator position read back from the transducer, in transducer
units.
READBACK_D (Scaling, Tuning)
The transducer state for the actual discrete valve or actuator position.
RESET (Tuning)
The time constant for the integral component of the PID block. It is
measured in seconds per repeat (so larger values have less effect, and
INF
effectively disables the integral term).
RESTART (Diagnostic, Option)
Allows the user to restart the device remotely.
Caution
Using
Restart
to
Defaults
causes all your configured parameters in the
FP-3000 to revert to their factory default settings.
Table 4-19. Restart Values
Value
Behavior
Restart
Resource
Restarts the device.
Restart
to
Defaults
Restarts the device, restoring all parameter values to default values.
Restart
Processor
Restarts the device as if the power was cycled.