Bkcal_out (process), Bkcal_out_d (process), Block_alm (alarming, diagnostic) – National Instruments NI-FBUS User Manual
Page 77: Block_err (diagnostic), Table 4-10. error codes

Chapter 4
Parameters
NI-FBUS Configurator User Manual
4-12
ni.com
BKCAL_OUT (Process)
A back-calculation value published to the
BKCAL_IN
of an upstream block
in a control loop. The
BKCAL_OUT
parameter has the value of the block’s
current output. Before a cascade loop is initialized, the upstream block can
use this value to smoothly transfer to loop control.
BKCAL_OUT_D (Process)
An output value published to an upstream discrete block. The upstream
block can use this value to smoothly transfer to loop control.
BLOCK_ALM (Alarming, Diagnostic)
An alarm parameter used to report error conditions detected within the
block, such as block Out of Service.
BLOCK_ERR (Diagnostic)
A list of error conditions for hardware and software components associated
with the block.
Table 4-10. Error Codes
Error Code
Code
Description
Other
0x0001
Undefined block error condition.
Block Configuration Error
0x0002
The block has detected an error in its
configuration. This usually indicates a
static parameter has been left uninitialized.
Link Configuration Error
0x0004
The logical connection between this block
and another block is misconfigured.
Simulate Active
0x0008
For I/O function blocks, this indicates that
simulation is enabled. For the resource
block, this indicates that the simulate
jumper has been set, allowing simulation to
be enabled in other blocks.
Local Override
0x0010
The block has locally overridden the output
value. This can be the result of an interlock
or faultstate.
Device Faultstate Set
0x0020
The block faultstate behavior is active.