BYPASS (Scaling, Tuning)
Allows the normal control algorithm to be bypassed. If control is bypassed,
the PID uses its setpoint value in percent of scale as its output value and
does not attempt to do any PID control.
Note
The
CONTROL_OPTS Bypass Enable
option must be selected.
Device Needs Maintenance Soon
0x0040
The device is reporting performance
degradation that will soon require
maintenance.
Input Failure/BAD PV Status
0x0080
Either the input transducer channel has
reported a failure, or the input parameter
from an upstream block has reported a
failure. For an AI block, this could be
caused by an open circuit being detected on
the FP-AI-100 input module.
Output Failure
0x0100
The output transducer channel has reported
a failure. For an AO block, this could
indicate that the FP-AO-200 cannot drive
the current request, perhaps due to an open
circuit.
Memory Failure
0x0200
The storage for nonvolatile and static
parameters was corrupted.
Lost Static Data
0x0400
The device was unable to restore the values
of static parameters after a restart.
Lost NV Data
0x0800
The device was unable to restore the values
of nonvolatile parameters after a restart.
Readback Check Failed
0x1000
The value read back from the output
channel does not match the value the
output channel was set to.
Device Needs Maintenance Now
0x2000
The device needs to be maintained now.
Power-Up
0x4000
The device has just powered up.
Out of Service
0x8000
The block is currently out of service.