Mode Problems
A function block alternates between
Iman
and
Auto
modes.
The status of the input parameter is
Bad::No comm
.
The function block and communication schedules do not have enough time
between them. Complete the following steps:
1.
Edit the schedule to add more time between the function block and
communication schedules. To edit the schedule, double-click the
Schedule icon in the configuration tree.
For more information about editing the schedule, refer to the
section of Chapter 2,
2.
After you edit the schedule, select Configure»Download
Configuration to download the changes.
For more information about downloading the configuration, refer to
the
Download a Project Configuration
section of Chapter 2,
The PID does not transition to
Auto
mode.
If the status of an
OUT
or
BKCAL_OUT
parameter on an AI or AO block is
Bad::Not Connected
or
Bad::No Comm
, or the downstream block is
not in cascade mode, complete the following steps:
1.
Use the Monitor mode to make sure that the AI and AO blocks are
publishing correct values.
2.
Make sure that the LAS executes the communication schedule. Use
monitoring mode to view the modes, inputs, and outputs of the block.
If the LAS is not executing the schedule, select Configure»Download
Configuration to download the configuration.