Cas_in (process), Cas_in_d (process), Channel (i/o, process) – National Instruments NI-FBUS User Manual
Page 79: Clr_fstate (faultstate, option), Confirm_time (alarming), Control_opts (option, scaling), Table 4-11. control options

Chapter 4
Parameters
NI-FBUS Configurator User Manual
4-14
ni.com
CAS_IN (Process)
A remote setpoint value. If used, will be linked to an output of an upstream
block. In some blocks, may be left unlinked, and a local setpoint value
(typically SP) will be used instead.
CAS_IN_D (Process)
A remote setpoint value. If used, will be linked to an output of an upstream
block. In some blocks, may be left unlinked, and a local setpoint value
(typically
SP_D
) will be used instead.
CHANNEL (I/O, Process)
Used by I/O function blocks to select a physical I/O channel. This mapping
is defined by the manufacturer. In the FP-3000, this parameter is
automatically updated when the
FIELDPOINT_MODULE
and
FIELDPOINT_CHANNEL
parameters are modified.
CLR_FSTATE (Faultstate, Option)
Writing Clear to this parameter causes the device-wide faultstate to be
cleared and output blocks to resume normal execution. Also refer to the
SET_FSTATE
and
FAULT_STATE
parameters.
CONFIRM_TIME (Alarming)
The lower bound on the time the device waits to send alert report messages
if no confirmation is received from a host.
CONTROL_OPTS (Option, Scaling)
A list of options used to adjust the way control blocks, such as the PID
block, operate.
Table 4-11. Control Options
Options
Description
Bypass Enable
If set, lets you set the
BYPASS
parameter and bypass the
algorithm’s control.
SP-PV Track in Man
Causes the setpoint to track the process variable in
Man
.
SP-PV Track in ROut
Causes the setpoint to track the process variable in
ROut
.
SP-PV Track in LO or IMan
Causes the setpoint to track the process variable in
LO
or
IMan
.