Appendix B
Troubleshooting and Common Questions
NI-FBUS Configurator User Manual
B-2
ni.com
For more information about downloading the configuration, refer to
the
Download a Project Configuration
section of Chapter 2,
3.
Make sure the target mode of both the PID and AO blocks is set to
Cas
.
The AI block does not transition to
Auto
mode from
OOS
mode.
The configuration is incorrect or incomplete. Complete the following steps:
1.
Make sure that the resource block is in
Auto
mode.
2.
Make sure the
XD_SCALE
fields are set to the value specified by the
vendor.
3.
Set the target mode of the AI block to
Auto
.
The function blocks are in
OOS
mode.
The resource block is in
OOS
mode. Set the target mode of the resource
block to
Auto
, then set function block to their normal mode.
AI block will not go to
Auto
Mode.
The block must be scheduled to execute (done by placing it in the Function
Block Application Editor window and downloading) before it can go into
Auto
mode. If the block still will not go into
Auto
, try the following
solutions:
•
Check that the resource block is in
Auto
.
•
Look at the
BlockError
parameter on the Diagnostics tab. This will
often give reasons for staying in
OOS
mode.
•
For FieldPoint, you can look at the
LAST_BLOCK_EVENT
parameter.
•
Make sure that the parameter
L_TYPE
has been initialized and other
parameters are set properly.
When using an FP-3000 with a PID block cascade, the high limit flag
goes ON as it should when the output reaches the high limit, but it stays
ON even when that output goes back down.
Reduce the
BKCAL_HYS
parameter. When outputs hover around alarm
limits, this triggers the alarm to turn on and off. After an alarm has been
triggered, this parameter specifies how far below the alarm limit the output
must fall before the alarm condition will clear. Setting this to zero means
that as soon as the output falls below the alarm limit, the condition will
clear.