Installation

2-5

3163-A2-GB20-10

March 1999

Installing the Redundant –

ā

48 Vdc Power

Supply

To install the DSU/CSU using a redundant – 48 Vdc

power supply, refer to Figure 2-5 and use the following
procedure.

"

Procedure

To install the redundant – 48 Vdc power supply:

1. Connect the black wire to the – 48 Vdc return

source B.

2. Connect the red wire to the – 48 Vdc return

source A.

3. Connect the green wire to a suitable ground.

4. Connect the orange wire to the – 48 Vdc input

source B.

5. Connect the blue wire to the – 48 Vdc input

source A.

6. Cut the white wire off at the outer insulation.

7. Plug the power connector into the DSU/CSU.

1

2

3

4

5

6

BLACK

RED

GREEN

WHITE

ORANGE

BLUE

– 48 VDC RETURN B

– 48 VDC RETURN A

GROUND

– 48 VDC INPUT B

– 48 VDC INPUT A

99-14300-02

X

DSU/CSU POWER

PLUG

TO CUSTOMER-SUPPLIED BATTERY

Figure 2-5. –

ā

48 Vdc Redundant Source Power Supply Pinouts