beautypg.com

Siemens Industrial Ethernet Switches SCALANCE X-200 User Manual

Page 252

background image

PROFINET IO functionality

8.2 Settings in HW Config

SCALANCE X-200

252

Operating Instructions, 12/2011, A5E00349864-19

● You want to use MRP in a ring topology only with Siemens devices and without

monitoring diagnostic interrupts:
Assign all devices to the "default-mrpdomain".
The device that actually takes over the role of redundancy manager, is negotiated by

Siemens devices automatically.

● You want to use MRP in a ring topology that also includes non-Siemens devices or you

want to receive diagnostic interrupts relating to the MRP status from a device (see

"Diagnostic interrupts"):
– Select the "Manager" role for one device (and one only) that will be redundancy

manager in the ring.

– For all other devices in the ring topology, select the role of "Client".

NOTICE

Using a non-Siemens device
To ensure problem-free operation when using a non-Siemens device as the

redundancy manager in the ring, make sure that you assign the fixed role of "Client"

to all other devices in the ring, before you close the ring. Otherwise, there may be

circulating data frames that will cause a failure in the network.

● You want to disable MRP:

Select the option "Not node in the ring" if you do not want to operate the device within a

ring topology with MRP.

Ring port 1 / ring port 2

Here, select the port you want to configure as ring port 1 and ring port 2.
The drop-down list shows the selection of possible ports for each device type. If the ports are

specified in the factory, the boxes are grayed out.

Note
With X200 switches with more than 8 ports, not all ports can be selected as ring port.

NOTICE

Effects of resetting to factory settings
If you reset to the factory settings, the ring port settings are also reset. With the appropriate

attachment, a previously correctly configured ring node can cause circulating frames and

therefore the failure of the data traffic.

Diagnostics interrupts

Select the "Diagnostics interrupts" option, if you want diagnostics interrupts relating to the

MRP status on the local CPU to be output.